4. With DHW set. LED display shows number 50 – it represents current HUW temperature set on
boiler (bottom line visible on display).
↑
Increase required temperature,
↓
decrease required
temperature, confirm required temperature,
→
go to CH temperature setting.
5. LED display shows number 20 – it represents current CH temperature set on boiler (upper line
visible on display).
↑
Press once – temperature read starts to pulse,
↑
increase required
temperature,
↓
decrease required temperature,
confirm required temperature,
→
go to P01
function.
P01 – Boiler power – manual distribution
Shows current boiler power setting,
↑
increase power (67%, 100%),
↓
decrease power (67%,
33%), confirm setting (100% is recommended),
→
go to P02 function.
P02 – Pump operation time setting
Shows current pump operating time,
↑
increase operating time,
↓
decrease operating time,
confirm setting (10 is recommended), ON parameter on display sets continuous pump
operation independently of boiler heaters operation status,
→
go to P03 function.
P03 – PID controller
Shows current PID setting,
↑
increase coefficient
↓
decrease coefficient, confirm setting (3
is recommended),
→
go to P04 function.
Note: if it takes too long for boiler to reach required
temperature, set coefficient on 4 or 5 and to 1 or 2 if the increase is too fast.
P04 – Maximum boiler operating temperature - CH
Shows set operating temperature,
↑
increase temperature up to 70°C (95°C for AsHZ and
ASBIII only),
↓
decrease temperature,
confirm setting (70 is recommended),
→
go to P05
function.
P05 – Maximum boiler operating temperature – DHW (with DHW set only)
Shows set
operating temperature,
↑
increase temperature up to 65°C,
↓
decrease temperature down to 5°C,
confirm setting (50 is recommended),
→
go to P06 function.