10 .10 .4 Function of terminal 66
Parameter 71
Parameter 71 = 0: Off.
Parameter 71 = 8: AND with input at terminal 46 (emergency
stop).
Parameter 71 = 20: LDS ignition position check.
The BCU does not perform a burner start-up, restart or start-up
attempt until the butterfly valve is in ignition position. To ensure
that the burners only start with the start-up fuel rate, the FCU
issues an enable signal to start the burner via terminal 66 to
the BCU with setting P71 = 20. In addition, the safety interlocks
must have been enabled by the FCU.
BCU
BCU
FCU
µC
54 55
53
+24V
M
L1
L1
54 55
53
M
66
66
10 .10 .5 Function of terminal 67
Parameter 72
Parameter 72 = 0: Off.
Parameter 72 = 8: AND with input at terminal 46 (emergency
stop).
10 .10 .6 Function of terminal 68
Parameter 73
Parameter 73 = 0: Off.
Parameter 73 = 8: AND with input at terminal 46 (emergency
stop).
Parameters > Functions of terminals 50, 51, 65, 66, 67 and 68