BCU 580 · Edition 11.15
109
14 .2 Function
The OCU features an illuminated plain-text display. The lighting
is switched on when a control key is pressed and switches
off automatically after 5 minutes. In case of a fault lock-out
or safety shut-down of the control unit, the OCU light starts
blinking.
You can choose between the indicating ranges “status dis-
play” and “Service mode”.
The status display shows the program step or a fault message
which has occurred in text form with the appropriate code.
The Service mode allows you to read out process values, pa-
rameter settings, information on the OCU or the statistics. In
addition, you can operate connected control units in Manual
mode.
There are five control keys for the OCU and the control unit
connected to it:
OK
ON/OFF
Use the ON/OFF key to switch the control unit on or off.
OK
Reset
Use the Reset key to reset the control unit to its starting
position in the event of a fault.
OK
OK
Press the OK key to confirm a selection or query.
Starting from the status display, you can use the
OK key to change to Service mode.
OK
Back
In Service mode, you can use the Back key to switch
from one setting level to the next higher one.
By holding down the key for a certain time, you can
change directly to the status display.
OK
Navigation UP/DOWN
In Service mode, the navigation keys can be used to
select individual functions on one level.
In Manual mode, those keys can be used to open
and close an activated butterfly valve.
14 .2 .1 Manual mode
In Manual mode, the control unit works with capacity control
(FCU..F1/F2 or BCU..F1/F2) regardless of the status of its inputs.
The inputs for start-up signal (terminal 1), controlled air flow
(terminal 2) and remote reset (terminal 3) are ignored. The
function of the controller enable/emergency stop input (ter-
minal 46) is retained.
The positions for maximum capacity, minimum capacity and
ignition capacity of an actuator can be adjusted using the OCU.
The OCU supports the process by means of a cyclic, automatic
repeat approach to the selected position. The actuator can be
moved within the menu to make changes to the cam settings.
After start-up has been completed, the navigation keys can
be used, for example, to open or close a butterfly valve in
program step
04
.
OCU