BCU 580 · Edition 11.15
50
10 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Parameter Value range
Description
Factory default
settings
Burner 1 FS1 flame signal switch-off
01
0 – 20
Burner 1 FS1 flame signal switch-off thresh-
old in µA
2
(5 when P04 = 1)
Burner 2 flame signal switch-off
02
0 – 20
Burner 2 FS2 flame signal switch-off thresh-
old in µA
2
(5 when P04 = 1)
04
0
1
2
3
4
5
6
7
8
Ionization
UVS
UVD
Ionization1 and UVS 2
Ionization1 and UVD 2
UVS 1 and ionization 2
UVD 1 and UVD 2
UVD 1 and ionization 2
UVD 1 and UVS 2
0
06
0
2
3
Off
Intermittent operation with UVS
Continuous operation with ionization/UVD
0
07
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
08
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
▼