BCU 580 · Edition 11.15
77
Parameter 40 = 5: with air valve.
The positions for maximum capacity and ignition capacity can
be set using the air valve. If the air valve is closed, the igni-
tion capacity is reached, if it is open, the maximum capacity
is reached.
BCU 580..F3
µC
VAS
VAS 1
VAG
TZI/TGI
VR..L
V1
V2
V4
10
9
13
14
57
8
5
Parameter 42 (Running time) can be used to adjust the be-
haviour of slow opening and closing air valves so that the
system can be set to ignition position before a start-up is
initiated. Parameter 41 (Running time selection) must be set
to 1 to adjust this behaviour.
See page 78 (Running time) and (78 (Running time se-
Parameters > Air control > Capacity control