Supply Voltage Unbalance OK/FAIL:
Voltage unbalance is evaluated at intervals of 10 min.
within observation window of 1 week. Evaluation is only at intervals in which voltage is inside
nominal boundary of [+15.0%,-15.0%]. Unbalance limit N1 is set to 2.00% and must be kept
95.0% of observation time. Intervals with voltage interruption are discarded. Intervals with
DIPS or Over voltage are discarded.
COMPLIANCE SUMMARY SECTION:
The Compliance Type
is configured when Setting your Instrument in PQ Compliance
Configuration.
Running Status
means whether or not the BLACKBOX’s Power Quality engine is evaluating the
power quality according to the Configured PQ Compliance.
The
Embedded Report
field further indicates a type of report that is auto-generated
internally in the device's file system. Most compliance types do not generate any specific
report, & therefore, the report type will be
None
. However, CREG type of compliance (used
in Colombia) also auto-generates a specific format of Report Files as defined by the local
regulator.
The Evaluation Status
field provides an overall status of PASS or FAIL of the entire
compliance. Anytime the evaluation period is not complete (typically required is a 1 week
observation), the status will be
N/A
(Not Available), otherwise PASS will be indicated as
OK.
The Start Time
field shows the last time the compliance engine was restarted. The entire
state & observation window history is stored on the internal non-volatile memory, so even
after powering down; the Engine will continue its evaluation & maintain all indications.
(Start time remains unchanged after device powered up.)
The Window Time On/Off
fields specify how much aggregated time is already in the
observation window.
ON
refers to the aggregated window time the device was powered on &
OFF
refers to the amount of window time the device power was off. The format presented
is [Days: Hours: Minutes: Seconds]. Ideally the
OFF
time is all zeroes & the
ON
time is 7 days
(which is the typical full observation period in most of the compliance types). Once the
observation window reaches 7 days, it will start to slide in steps of 2 hours. Sliding means
the information from the oldest 2 hours is being dropped, where a new up-to-date 2-hour
interval is being used for calculations.
The Measurement Flag
field indicates whether there is a power quality event such as a
DIP/SWELL
or
INTERRUPTION
at the moment.
Содержание G3500 BlackBox
Страница 1: ...1 ...
Страница 19: ...19 See also What You ll Need Unpacking Components Accessories G4500 BLACKBOX Unit G3500 BLACKBOX Unit ...
Страница 32: ...32 See also Safety Precautions What You ll Need Unpacking Components Accessories G4500 BLACKBOX Unit ...
Страница 38: ...38 2Phase TR SINGLE SPLIT PHASE delta 3 wires THREE WIRE DELTA ...
Страница 39: ...39 delta 3 wires Grounded Delta wye 4 wires four wire wye ...
Страница 40: ...40 wye 4 wires three wire wye Delta 3 wires delta high leg ...
Страница 82: ...82 The Average Window will now open ...
Страница 96: ...96 The Waveforms Window will now open ...
Страница 113: ...113 Export Dialog Various Export Options ...
Страница 130: ...130 The window containing the table for V I Min Max Harmonics values will now open ...
Страница 142: ...142 About PQ Monitoring Compliance Summary Compliance Chart Events PQ Compliance Configuration ...
Страница 171: ...171 SEE ALSO About Energy Measurement Status ...
Страница 207: ...207 SEE ALSO About the Current Window Current Probes Info Non Measured Currents ...
Страница 217: ...217 Open the LAN Tab Select or complete the following in the applicable sections select ...
Страница 220: ...220 You should now be able to identify the Router on your computer s Network Sharing Center ...
Страница 247: ...247 ...
Страница 327: ...327 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Страница 331: ...331 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Страница 334: ...334 SEE ALSO About Battery Replacement G3500 BLACKBOX Unit G4500 BLACKBOX Unit ...
Страница 345: ...345 SEE ALSO About Elspec s Search Utility Obtain the Utility Use the Utility New Device Indication Limitations ...
Страница 352: ...352 Connector Type RJ45 Female With Led Indicators Power Over Ethernet PoE Out 1 Available as Output 13 Watt DC 48V ...
Страница 357: ...357 DIMENSIONAL VIEW G4500 ...
Страница 358: ...DIMENSIONAL VIEW G3500 SEE ALSO G4500 G3500 Specifications ...