13
Setting the parameters
Cala KNX M-T push button
• Version: 13.09.2019 • Technical changes and errors excepted.
The
minimum and maximum readings
can be saved and sent to the bus. Use the
"Reset temperature min/max. value" objects to reset the values to the current readings.
The values are not retained after a reset.
5.4. Push button
On Cala KNX M2-T and Cala KNX M4-T there is a screen control with an additional func-
tion. It is activated by simultaneously touching two (Cala KNX M2-T) or three or four
(Cala KNX M4-T) push buttons. The value of the activation object and the function is
set for the screen control.
Set whether you want to use the screen control.
Enable the push button The menus for the other settings of the push buttons are shown
on them.
At and above change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • ... • 5.0°C
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use minimum and maximum value
No • Yes
Use screen control
No • Yes
Use screen control
Yes
Activation object assessment
• Value 1 = active | Value 0 = inactive
• Value 0 = active | Value 1 = inactive
Object value after reset
0 • 1
Function
• Switch
• Selector switch
• 8 bit value 0 ... 255
• 8 bit value 0 ... 100%
• 16-bit floating point value
• Scenario recall
Value (
switch
)
0 • 1
Value (
8 bit value 0 ... 255
)
0 • ... • 255
Value (
8 bit value 0 ... 100%
)
0 • ... • 100
Value in 0.1 (
16 bit value floating point
)
-6707600 • ... • 6707600; 10
Scenario number(
Scenario recall
)
1 • ... • 64
Use push button 1 (top left)
No • Yes
Use push button 2 (top right)
No • Yes
Use push button 3 (bottom left)
No • Yes
Use push button 4 (bottom right)
No • Yes