Target value setpoint per
Parameter • Communication object
If the target value is set per Parameter:
Target value setpoint per
Parameter
Target value heating in 0.1°C
(if the heating control is used)
-300 … 800
Target value cooling in 0.1°C
(if the cooling control is used)
-300 … 800
If the target value is set per Communication object:
Target value setpoint per
Communication object
The value communicated last shall be
maintained
• not
• after restoration of voltage
• after restoration of voltage and programming
(Do not use for first commissioning)
Start target value heating in 0.1°C
valid until 1.communication
(if the heating control is used and only if the
value communicated last is “not” maintained
or “after restoration of voltage”)
-300 … 800
Limitation of object value H(min) in 0.1°C
-300 … 800
Limitation of object value H(max) in 0.1°C
-300 … 800
Start target value cooling in 0.1°C
valid until 1.communication
(if the cooling control is used and only if the
value communicated last is “not” maintained
or “after restoration of voltage”)
-300 … 800
Limitation of object value C(min) in 0.1°C
-300 … 800
Limitation of object value C(max) in 0.1°C
-300 … 800
Type of the target value change
• Absolute value
• Increment/decrement
Step size
(only with “Increment/decrement”)
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C • 2°C •
3°C • 4°C • 5°C
Frost/heat protection
……………………………
Use frost/heat protection
No • Yes
If frost/heat protection is used:
Use frost/heat protection
Yes
Target value heating in 0.1°C
(only if heating control is used)
-300 … 800
Delay of activation
(after opening window)
none • 1 s … 2 h
Target value cooling in 0.1°C
(only if cooling control is used)
-300 … 800