18
If the control is in use:
Control general:
……………………………
Type of control
• One-stage heating
• Two-stage heating
• One-stage cooling
• One-stage h one-stage cooling
• Two-stage h one-stage cooling
• Two-stage h two-stage cooling
Behaviour of the blocking object with value
• 1 = block control |
0 = release control
• 0 = block control |
1 = release control
Value of the blocking object
before 1. communication
0 • 1
Send actuating variables
• on change
• on change and periodically
Transmission cycle
(only if sending „periodically“)
5 s … 2 h
Status object/s send
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Transmission cycle
(only if sending „periodically“)
5 s … 2 h
Controller target value:
……………………………
Target value setpoint per
Parameter • Communication object
If the target value is set per Parameter:
Target value setpoint per
Parameter
Target value in 0.1°C
-300 … 800
If the target value is set per Communication object:
Target value setpoint per
Communication object
The value communicated last shall be
maintained
• not
• after restoration of voltage
• after restoration of voltage and programming
(Do not use for first commissioning)