27
OR Logic 1 / 2 / 3 / 4
1. / 2. / 3. / 4. Input
• do not use
• all switching events which the sensor
provides (see “Linkage inputs of the AND
logic”)
Logic output sends
one 1 bit object • two 8 bit objects
If the logic output sends one 1 bit object:
Logic output sends
ein 1 Bit-Objekt
If logic = 1
Î
object value
1 • 0
If logic = 0
Î
object value
0 • 1
Communication object
OR Logic 1 / 2 sends
• on change of logic
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
Send periodically all
(only if sending “periodically”)
5 s • 10 s • 30 s • 1 min • … • 2 h
If the logic output sends two 8 bit objects:
Logic output sends
two 8 bit objects
If logic = 1
Î
object A value
0 … 255
If logic = 0
Î
object A value
0 … 255