15
The value communicated last shall be
maintained
• not
• after restoration of voltage
• after restoration of voltage and programming
(Do not use for first commissioning)
Start temperature threshold value in 0.1°C
valid until 1.communication
(only if the value communicated last is “not”
maintained or “after restoration of voltage”)
-300 … 800
Type of threshold change for temperature
• Absolute value
• Increment/decrement
Step size
(only with “Increment/decrement”)
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C • 2°C •
3°C • 4°C • 5°C
Hysteresis of the threshold value in %
0 … 50
Temperature switching output:
……………………………
Output is at
(TV = temperature threshold value)
• TV above = 1 | TV – Hyst. below = 0
• TV above = 0 | TV – Hyst. below = 1
• TV below = 1 | TV + Hyst. above = 0
• TV below = 0 | TV + Hyst. above = 1
Switching delay from 0 to 1
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Temperature switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send temperature switching output
in the cycle of
(only if sending “periodically”)
5 s • 10 s • 30 s • 1 min • … • 2 h
Blocking:
……………………………
Use block of the temperature switching output
No • Yes
Evaluation of the temperature blocking object
• if value 1: block | if value 0: release
• if value 0: block | if value 1: release
Wert des Sperrobjekts
vor 1. Kommunikation
0 • 1
Behaviour of switching output
with blocking
• do not send telegram
• send 0
• send 1
Содержание KNX T-AP
Страница 1: ...Temperature Sensor KNX T AP Installation and Adjustment ...
Страница 3: ...2 ...