Description

Indoor Sensor KNX AQS/TH

 • Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.

1. Description

The 

Indoor Sensor KNX AQS/TH

 measures the room CO

2

 concentration, the tempe-

rature und air humidity and calculates the dew point. The sensor can receive external 
values for temperture, humidity and CO

2

 via the bus and process them with the own 

data to overall values (mixed values, e. g. room average). 

The 

KNX AQS/TH

 provides eleven switching outputs with adjustable threshold valu-

es. The switching outputs and further communication objects can be linked by AND 
and OR logic gates. Additionally, an integrated actuating variable comparator can com-
pare and output values that are received via communication objects.

Integrated PI controllers allows for control of a ventilation (depending on CO

2

 concen-

tration and air humidity) and a heating/cooling system (depending on temperature). 
The sensor can can emit a warning to the bus as soon as the area of optimum comfort 
(according to DIN 1946) is left. 

Functions:

Measurement of 

CO

2

 concentration

 of the air, of 

temperature

 and 

air 

humidity

 (absolute, relative), calculation of the dew point 

Mixed values

 from own measured values and external values (proportions 

can be set in percentage) 

PI controller for heating

 (one or two step) and 

cooling

 (one or two step) 

depending on temperature 

PI controller for ventilation

 depending on humidity and CO2 concentration: 

dehumidification/humidification (one step) or dehumidification (one or two 
step)

11 switching outputs

 with adjustable threshold values (Threshold values 

can be set by parameter or via communication objects)

8 AND and 8 OR logic gates

 with each 4 inputs. Every switching incident as 

well as 8 logic inputs (in the form of communication objects) may be used as 
inputs for the logic gates. The output of each gate may optionally be configured 
as 1 bit or 2 x 8 bits

2 actuating variable comparators

 for output of minimum, maximum or 

avarage values. Each with 5 inputs (for values received via communication 
objects)

Configuration is made using the KNX software ETS. The 

programme file

 (format VD), 

the data sheet and the manual can be downloaded from the Elsner Elektronik home-
page on 

www.elsner-elektronik.de

 in the “Service” menu.

1.0.1. Measurement of carbon dioxide in the air

The CO

2

 concentration in the air is indicated in parts per million (ppm). 1000ppm cor-

respond to 0.1%. From this value on humans perceive the room air as „used“.

Содержание KNX AQS/TH

Страница 1: ...ment EN Elsner Elektronik GmbH Control and AutomationTechnology Herdweg 7 D 75391 Gechingen Phone 49 0 70 56 93 97 0 info elsner elektronik de Germany Fax 49 0 70 56 93 97 20 www elsner elektronik de KNX AQS TH Indoor Sensor ...

Страница 2: ...unication objects 10 4 Setting of parameters 19 4 1 General settings 19 4 2 Temperature measured value 19 4 3 Temperature threshold values 20 4 3 1 Threshold values 1 2 3 4 20 4 4 Temperature PI control 22 4 5 Humidity measured value 26 4 6 Humidity threshold values 27 4 6 1 Humidity threshold values 1 2 27 4 7 Humidity PI control 29 4 8 Dewpoint temperature 30 4 8 1 Monitoring of the cooling medi...

Страница 3: ...ion Advice on dangers concerning work on electrical terminals components etc Safety measures to protect the life and health of relevant personnel Safety instruction Instructions that must strictly be observed to ensure the safe operation Safety measures to protect against damage to persons or property ...

Страница 4: ...tive calculation of the dew point Mixed values from own measured values and external values proportions can be set in percentage PI controller for heating one or two step and cooling one or two step depending on temperature PI controller for ventilation depending on humidity and CO2 concentration dehumidification humidification one step or dehumidification one or two step 11 switching outputs with...

Страница 5: ... scope of delivery Protection category IP 50 Dimensions Cover approx 94 94 W H mm mounting depth approx 8 mm Weight approx 105 g including box and cover Ambient temperature Operation 10 50 C Storage 20 60 C Ambient air humidity approx 95 rF avoid bedewing Operating voltage KNX bus voltage Bus current max 10 mA Data output KNX Bus terminal plug BCU type own micro controller PEI type 0 Group address...

Страница 6: ... once in this period After this the CO2 sensor will recalibrate every two weeks by defining the lowest mea sured value captured during that period without interruption of the bus voltage as a reference for fresh air The guarantee the accuracy on a sustained basis the sensor should be provided with fresh air at least once in two weeks This occurs normally during room ventilation 2 Installation and ...

Страница 7: ...ht of head standing or sitting according to utilization of room The CO2 concen tration in indoor rooms is highest near the floor and decreases towards the ceiling When selecting an installation location please ensure that the measurement results are affected as little as possible by external influences Possible sources of interference include Direct sunlight Drafts from windows and doors Draft fro...

Страница 8: ...ice screw Ø 3 2 mm 15 mm 1x Cover with punches 1x Board with sensor electronic and connection plugs bus black red axiliary voltage white yellow 1x Distribution box Ø 70 mm 36 mm deep 1 Grooves for attachment of cover 2 Oblong holes for fastening with distribution box 3 Programming button for teaching the device can also be operated when cover is clamped on see right 4 Programming LED 3 2 1 4 3 4 ...

Страница 9: ...the box First mount the box and connection lead Subsequently connect the bus connector black red to the intended terminal of the sensor board Screw the sensor board in the box Now clamp the cover with the snap taps in the grooves of the board Screw holes on left and right Logo on top of board Logo on top of cover 1 Grooves for attachment of cover 2 Oblong holes for fastening with distribution box ...

Страница 10: ...of issue 13 10 2011 Subject to technical changes Errors excepted 2 5 Notes on assembly and operation Sensor must not be exposed to water rain or dust This could result in the electronic being damaged A relative air humidity of 95 must not be exceeded Avoid bedewing ...

Страница 11: ...otal measured value for temperature Output 9 001 C R T 6 Request min max temperature mea sured value Input 1 017 C W 7 Minimum measured value for tem perature Output 9 001 C R T 8 Maximum measured value for tem perature Output 9 001 C R T 9 Reset min max measured value for temperature Input 1 017 C W 10 Temp threshold value 1 Absolute value Input output 9 001 C R W T U 11 Temp threshold value 1 1 ...

Страница 12: ...ut Output 1 001 C R T 27 Temp threshold value 3 Switching output block Input 1 002 C W 28 Temp threshold value 4 Absolute value Input output 9 001 C R W T U 29 Temp threshold value 4 1 0 Input 1 002 C W 30 Temp threshold value 4 Switching delay from 0 to 1 Input 7 005 C W 31 Temp threshold value 4 Switching delay from 1 to 0 Input 7 005 C W 32 Temp threshold value 4 Switching output Output 1 001 C...

Страница 13: ...ting night 1 0 Input 1 002 C W 50 Temp control Target value Cooling night Input output 9 001 C R W T U 51 Temp control Target value Cooling night 1 0 Input 1 002 C W 52 Temp control Status heating 1 1 ON 0 OFF Output 1 001 C R T 53 Temp control Status heating 2 1 ON 0 OFF Output 1 001 C R T 54 Temp control Status Cooling 1 1 ON 0 OFF Output 1 001 C R T 55 Temp control Status Cooling 2 1 ON 0 OFF O...

Страница 14: ...old value 2 Switching delay from 1 to 0 Input 7 005 C W 74 Humidity threshold value 2 Switching output Output 1 001 C R T 75 Humidity threshold value 2 Switching output block Input 1 002 C W 76 Humidity control Blocking object Input 1 006 C W 77 Humidity control Target value Input output 9 007 C R W T 78 Humidity control Target value 1 0 Input 1 002 C W 79 Humidity control Actuating variable Dehum...

Страница 15: ...t 9 001 C R T 98 Total measured value for CO2 Output 9 001 C R T 99 Request min max CO2 value Input 1 017 C W 100 Maximum measured value for CO2 Output 9 001 C R T 101 Reset min max measured value for CO2 Input 1 017 C W 102 CO2 threshold value 1 Absolute value Input output 9 001 C R W T U 103 CO2 threshold value 1 1 0 Input 1 002 C W 104 CO2 threshold value 1 Switching delay from 0 to 1 Input 7 0...

Страница 16: ... from 0 to 1 Input 7 005 C W 123 CO2 threshold value 4 Switching delay from 1 to 0 Input 7 005 C W 124 CO2 threshold value 4 Switching out put Output 1 001 C R T 125 CO2 threshold value 4 Switching out put block Input 1 002 C W 126 CO2 control Blocking object Input 1 006 C W 127 CO2 control Target value Input output 9 007 C R W T 128 CO2 control Target value 1 0 Input 1 002 C W 129 CO2 control Act...

Страница 17: ...t Output B Output 5 010 C R T 150 AND Logic 1 Blocking Input 1 002 C W 151 AND Logic 2 1 Bit Switching output Output 1 002 C R T 152 AND Logic 2 8 Bit Output A Output 5 010 C R T 153 AND Logic 2 8 Bit Output B Output 5 010 C R T 154 AND Logic 2 Blocking Input 1 002 C W 155 AND Logic 3 1 Bit Switching output Output 1 002 C R T 156 AND Logic 3 8 Bit Output A Output 5 010 C R T 157 AND Logic 3 8 Bit ...

Страница 18: ...7 OR Logic 3 1 Bit Switching output Output 1 002 C R T 188 OR Logic 3 8 Bit Output A Output 5 010 C R T 189 OR Logic 3 8 Bit Output B Output 5 010 C R T 190 OR Logic 3 Blocking Input 1 002 C W 191 OR Logic 4 1 Bit Switching output Output 1 002 C R T 192 OR Logic 4 8 Bit Output A Output 5 010 C R T 193 OR Logic 4 8 Bit Output B Output 5 010 C R T 194 OR Logic 4 Blocking Input 1 002 C W 195 OR Logic...

Страница 19: ...ogic input 4 Input 1 002 C W 215 Logic input 5 Input 1 002 C W 216 Logic input 6 Input 1 002 C W 217 Logic input 7 Input 1 002 C W 218 Logic input 8 Input 1 002 C W 219 Logic input 9 Input 1 002 C W 220 Logic input 10 Input 1 002 C W 221 Logic input 11 Input 1 002 C W 222 Logic input 12 Input 1 002 C W 223 Logic input 13 Input 1 002 C W 224 Logic input 14 Input 1 002 C W 225 Logic input 15 Input 1...

Страница 20: ...ransmission delays after power up and programming for Measured values 5 s 10 s 30 s 1 min 2 h Threshold values and switching outputs 5 s 10 s 30 s 1 min 2 h Controller objects 5 s 10 s 30 s 1 min 2 h Logic outputs 5 s 10 s 30 s 1 min 2 h Maximum telegram quota 1 2 3 5 10 20 Telegrams per second Use temperature humidity malfunction object No Yes Use CO2 malfunction object No Yes Offset in 0 1 C 50 ...

Страница 21: ... and maximum value Values are not maintained after reset No Yes Use external measured value Yes Ext measured value proportion of the total measured value 5 100 in steps of 5 All following settings refer to the total measured value Internal and total measured value send not periodically on change on change and periodically From change of in relation to last measured value only if sending on change ...

Страница 22: ...rement Step size only if sending Increment decrement 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 1 0 C 2 0 C 3 0 C 4 0 C 5 0 C Hysteresis of the threshold value in 0 50 Output is at TV Threshold value TV above 1 TV Hyst below 0 TV above 0 TV Hyst below 1 TV above 1 TV Hyst above 0 TV above 0 TV Hyst above 1 Delays can be set via objects in seconds No Yes Switching delay from 0 to 1 only if delays are not set vi...

Страница 23: ...elegram if switching output 1 send 1 on change to 0 do not send telegram if switching output 0 send 0 on change and periodically send status of the switching output no selection on change to 1 and periodically if switching output 1 send 1 no selection on change to 0 and periodically if switching output 0 send 0 no selection Use control No Yes Type of control One stage heating Two Stage heating One...

Страница 24: ...etpoint per Parameter Communication object Target value setpoint per Parameter Target value in 0 1 C 300 800 Target value setpoint per Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and pro gramming Do not use for first commis sioning Start target value in 0 1 C valid until 1 Kommunikation only if the value communi...

Страница 25: ...target actual diffe rence of 5 C Re setting time 150 min Floor heating Maximum actuating variable is reached at target actual diffe rence of 5 C Re setting time240 min Fan convector Maximum actuating variable is reached at target actual diffe rence of 4 C Re setting time 90 min Electrical heating Maximum actuating variable is reached at target actual diffe rence of 4 C Re setting time 100 min Targ...

Страница 26: ...the actuating variable shall not be sent send a specific value Value in only if sending a specific value 0 100 With release the actuating variable follows the control Cooling ceiling Maximum actuating variable is reached at target actual diffe rence of 5 C Re setting time 240 min Target value difference between 1 and 2 stage in 0 1 C 0 100 Type of control of the 2 stage 2 point control PI control ...

Страница 27: ...ion of voltage and pro gramming Do not use for first commis sioning Start threshold value in 0 1 C valid until 1 communication only if the value communicated last is not maintained or after restoration of voltage 300 800 Limitation of object value min in 0 1 C 300 800 Limitation of object value max in 0 1 C 300 800 Type of threshold change Absolute value Increment decrement Step size only if sendi...

Страница 28: ... No Yes Use humidity threshold values 1 2 No Yes Threshold value setpoint per Parameter Communication object Threshold value setpoint per Parameter Threshold value in RH 0 100 Hysteresis of the threshold value in in relation to threshold value 0 50 Threshold value setpoint per Communication object The value communicated last shall be maintained not After restoration of voltage After restoration of...

Страница 29: ...on change to 1 on change to 0 on change and periodically on change to 1 and periodically on change to 0 and periodically Send switching output in a cycle of only if sending periodically 5 s 10 s 30 s 1 min 2 h Use block of the switching output No Yes Evaluation of the blocking object if value 1 block if value 0 release if value 0 block if value 1 release Value of the blocking object before 1 commu...

Страница 30: ...k control 1 release control Value of the blocking object before 1 communication 0 1 Transmission behaviour of actuating variables on change on change and periodically Transmission cycle only if sending periodically 5 s 10 s 30 s 1 min 2 h Status objects send on change on change to 1 on change to 0 on change and periodically on change to 1 and periodically on change to 0 and periodically Transmissi...

Страница 31: ...le is reached at target actual difference of 1 50 Re setting time in mins 1 255 If blocked the actuating variable shall not be send send a specific value Value in only if sending a specific value 0 100 With release the actuating variable follows the control Target value difference between 1 and 2 stage in 0 50 Maximum actuating variable is reached at target actual difference of 1 50 Hysteresis in ...

Страница 32: ...t is maintained not or after restoration of voltage 0 20 Step size for offset chnage per communica tion object 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 1 C 2 C 3 C 4 C 5 C Hysterese of the threshold value in 0 50 Threshold value sends not periodically on change on change and periodically From change of only if sending on change 0 1 C 0 2 C 0 5 C 1 0 C 2 0 C 5 0 C Transmission cycle only if sending periodical...

Страница 33: ... Yes Evaluation of the blocking object if value 1 block if value 0 release if value 0 block if value 1 release Value of the blocking object before 1 communication 0 1 Behaviour of the switching output With blocking do not send telegram send 0 send 1 Value of parameter switching output sends Setting options Behaviour of switching output with release on change do not send telegram send status of the...

Страница 34: ...e 0 1 g 0 2 g 0 5 g 1 0 g 2 0 g 5 0 g Transmission cycle only if sending periodically 5 s 10 s 30 s 2 h Use comfort field No Yes Transmission behaviour not periodically on change on change and periodically Transmission cycle only if sending periodically 5 s 10 s 30 s 2 h Maximum temperature in C Standard 26 C 25 40 Minimum temperature in C Standard 20 C 10 21 Maximum relative humidity in Standard ...

Страница 35: ... measured value 5 100 in steps of 5 All following settings refer to the total measured value Internal and total measured value send not periodically on change on change and periodically From change of in relation to last measured value only if sending on change 2 5 10 25 50 Transmission cycle only if sending periodically 5 s 10 s 30 s 1 min 2 h Use maximum value Values are not maintained after res...

Страница 36: ... TV Hyst below 1 TV above 1 TV Hyst above 0 TV above 0 TV Hyst above 1 Delays can be set via objects in seconds No Yes Switching delay from 0 auf 1 only if delays are not set via objects none 1 s 2 s 5 s 10 s 2 h Switching delay from 1 auf 0 only if delays are not set via objects none 1 s 2 s 5 s 10 s 2 h Switching output sends on change on change to 1 on change to 0 on change and periodically on ...

Страница 37: ...lly send status of the switching output no selection on change to 1 and periodically if switching output 1 send 1 no selection on change to 0 and periodically if switching output 0 send 0 no selection Use control No Yes Type of control One stage ventilation Two stage ventilation Behaviour of the blocking object with value 1 block control 0 release control 0 block control 1 release control Value of...

Страница 38: ...oration of voltage 400 5000 Limitation of object value min in ppm 0 5000 Limitation of object value max in ppm 0 5000 Type of the target value change Absolute value Increment decrement Step size in ppm only with Increment Decrement 1 2 5 10 20 50 100 200 Maximum actuating variable is reached at target actual difference of in ppm 100 4000 Re setting time in mins 1 255 Type of the target value chang...

Страница 39: ...nly if sending on change of output 1 2 5 10 20 25 Evaluation of the blocking object if value 1 block bei Wert 0 release if value 0 block bei Wert 1 release Value of the blocking object before 1 communication 0 1 Behaviour of the output With blocking do not send telegramm send value Value in 0 100 With release the output sends incl 2 seconds release delay the current value the current value after r...

Страница 40: ...tings depend on Type of objects Transmission behaviour on change of logic on change of logic to 1 on change of logic to 0 on change of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically on change of logic receipt of object on change of logic receipt of object and periodically Transmission cycle only if sending periodically 5 s 10 s 30 s 1 min 2...

Страница 41: ... 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic input 16 Logic input 16 inverted on change of logic to 0 do not send telegram if slogic 0 send value for 0 on change of logic and periodically send value for current logic status no selection on change of logic...

Страница 42: ...atus cooling 1inverted Temp control Status cooling 2 Temp control Status cooling 2 inverted Temp control Status night reduction Temp control Status night reduction inverted Temp control Status window Temp control Status window inverted Switching output humidity 1 Switching output humidity 1 inverted Switching output humidity 2 Switching output humidity 2 inverted Humidity control status dehumidifi...

Страница 43: ...l 0 127 if logic 1 Object A Value settings depend on Type of objects if logic 0 Object A Value settings depend on Type of objects if logic 1 Object B Value settings depend on Type of objects if logic 0 Object B Value settings depend on Type of objects Transmission behaviour on change of logic on change of logic to 1 on change of logic to 0 on change of logic and periodically on change of logic to ...

Страница 44: ...ching output AND logic 7 Switching output AND logic 7 inverted Switching output AND logic 8 Switching output AND logic 8 inverted Value of parameter Transmission behaviour Setting options Behaviour of switching output with release on change of logic do not send telegram send value for current logic status on change of logic to 1 do not send telegram if logic 1 send value for 1 on change of logic t...

Страница 45: ...n and Operation EN WS1000 Color Control System for Buildings and for Conservatories Elsner Elektronik GmbH Control and AutomationTechnology Herdweg 7 D 75391 Gechingen Phone 49 0 70 56 93 97 0 info elsner elektronik de Germany Fax 49 0 70 56 93 97 20 www elsner elektronik de ...

Отзывы: