24
Setting of parameters
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
Settings for „Preset applications“:
Control of heating 2nd stage: (two-stage heating only):
For PI control see control heating 1st stage.
Maximum actuating variable is reached at
target/actual difference of
(only if the controller is set by „controler
parameter“ )
1,0°C • 2,0 °C • 3,0°C • 4,0°C • 5,0°C
Re-setting time in minutes
(only if the controller is set by „controler
parameter“ )
1 … 255
If blocked, the actuating variable shall
• not be sent
• send a specific value
Value in %
(only if sending a specific value)
0 ... 100
With release the actuating variable follows the control
Hot water heating
• Maximum actuating variable is reached at target/actual diffe-
rence of 5°C
• Re-setting time 150 min
Floor heating
• Maximum actuating variable is reached at target/actual diffe-
rence of 5°C
• Re-setting time240 min
Fan convector
• Maximum actuating variable is reached at target/actual diffe-
rence of 4°C
• Re-setting time 90 min
Electrical heating
• Maximum actuating variable is reached at target/actual diffe-
rence of 4°C
• Re-setting time 100 min
Target value difference between 1. and 2.
stage in 0,1°C
0 … 100
Type of control of the 2. stage
• 2-point-control
• PI control
Hysteresis in 0,1°C
(only if 2-point control is used)
0 ... 100
Actuating variable is a
(only if 2-point control is used)
• 1 bit object
• 8 bit object
Value in %
(only if 2-point control is used and if the
actuating variable is a 8 bit object)
0 ... 100
If blocked, the actuating variable shall
• not be sent
• send a specific value
Value in %
(only if sending a specific value)
0 ... 100
With release the actuating variable follows the control