14
Transmission protokoll
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
87
Cooling medium temp.: Actual value
Input
9.001
C W
88
Cooling medium temp.: Offset change
(1:+ | 0:-)
Input
1.002
C W
89
Cooling medium temp.: Switching
delay from 0 to 1
Input
7.005
C W
90
Cooling medium temp.: Switching
delay from 1 to 0
Input
7.005
C W
91
Cooling medium temp.: Switching out-
put
Output
1.001
C R T
92
Cooling medium temp.: Switching out-
put block
Input
1.002
C W
93
Absolute Humidity [g/kg]
Output
14.005
C R T
94
Absolute Humidity [g/m³]
Output
14.005
C R T
95
Ambient climate Status: 1 =
comfortable | 0 = uncomfortable
Output
1.002
C R T
96
External measured value for humidity
Input
9.001
C W
97
Internal measured value for CO2
Output
9.001
C R T
98
Total measured value for CO2
Output
9.001
C R T
99
Request min./max. CO2 value
Input
1.017
C W
100
Maximum measured value for CO2
Output
9.001
C R T
101
Reset min./max. measured value for
CO2
Input
1.017
C W
102
CO2 threshold value 1: Absolute value
Input / output
9.001
C R W T U
103
CO2 threshold value 1: (1:+ | 0:-)
Input
1.002
C W
104
CO2 threshold value 1: Switching
delay from 0 to 1
Input
7.005
C W
105
CO2 threshold value 1: Switching
delay from 1 to 0
Input
7.005
C W
106
CO2 threshold value 1: Switching out-
put
Output
1.001
C R T
107
CO2 threshold value 1: Switching out-
put block
Input
1.002
C W
108
CO2 threshold value 2: Absolute value
Input / output
9.001
C R W T U
109
CO2 threshold value 2: (1:+ | 0:-)
Input
1.002
C W
110
CO2 threshold value 2: Switching
delay from 0 to 1
Input
7.005
C W
111
CO2 threshold value 2: Switching
delay from 1 to 0
Input
7.005
C W
112
CO2 threshold value 2: Switching out-
put
Output
1.001
C R T
No
Name
Function
DPT
Flags