Setting of parameters
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
If an external measured value is used:
4.3. Temperature threshold values
4.3.1. Threshold values 1 / 2 / 3 / 4
Threshold value
If the threshold value is set per Parameter:
Use external measured value
No
Measured value
• not
• periodically
• on change
• on change and periodically
From change of
(in relation to last measured value)
(only if sending „on change“ )
0,1°C • 0,2°C • 0,5°C • 1,0°C • 2,0°C • 5,0°C
Transmission cycle
(only if sending „periodically“)
5 s • 10 s • 30 s • 1 min • … • 2 h
Use minimum and maximum value
(Values are not maintained after reset)
No • Yes
Use external measured value
Yes
Ext. measured value proportion of the total
measured value
5% … 100% (in steps of 5%)
All following settings refer to the total measured value
Internal and total measured value send
• not
• periodically
• on change
• on change and periodically
From change of
(in relation to last measured value
(only if sending „on change“)
0,1°C • 0,2°C • 0,5°C • 1,0°C • 2,0°C • 5,0°C
Transmission cycle
(only if sending „periodically“ )
5 s • 10 s • 30 s • 1 min • … • 2 h
Use maximum value
(Values are not maintained after reset)
No • Yes
Use threshold value 1 / 2 / 3 / 4
No • Yes
Threshold value setpoint per
Parameter • Communication object
Threshold value setpoint per
Parameter
Threshold value in 0,1°C
-300… 800
Hysteresis of the threshold value in %
0 … 50