BSR-6055

Addressable optical electronic smoke detector

23 / 07 / 2003

23 / 07 / 2003

Technical Specifications

Main voltage
Standby consumption
Alarm consumption
Degrees of cover protection
Produced in accordance with
Operation temperature range
Humidity
Dimensions
Weight
Guarantee

14-30 V

1 mÁ

1.5 mA (with activation LED)

IP 20

EN 54

-20 to 60 C

o

Up to 95% relative humidity

102 (diam) x 48 mm

200 gr

2 years

Description

BSR-6055 is an optical electronic smoke detector. It co -operates only with BSR-

1116 panels. The device transmits an analogue value to the panel which depends

on the amount of the smoke that there is in the area. The analogue value is 100

with obscuration rate 2% per metre (small amount of smoke) and 120 with

obscuration rate 4% per metre (large amount of smoke).

The factory setting of the panel is to issue an alarm when the analogue value is

greater than 110. The user can change this analogue value from 100 (very sensitive

detector) up to 120 (average sensitive detector). Á red coloured LED that blinks

periodically in standby detection mode, is a power indication LED and indicator for

the good operation of the device. When a detector issues an alarm the LED lights.

When we sillence the sirens the LED remains lit to show us the detector that issued

the alarm.

+L
-L

+L
-L

A

P

12

34

56

78

ON

Loop

Loop

Loop

Loop

IN

IN

O

U

T

OU

T

R

IN

IN

O

U

T

OU

T

R

IN

IN

O

U

T

OU

T

R

IN

IN

O

U

T

OU

T

R

IN

IN

O

U

T

OU

T

R

IN

IN

O

U

T

OU

T

R

Common base for smoke and thermal detectors

The base that is included in the

package of the smoke and thermal

detectors has four contacts for cable

connections.

We connect the two contacts with

polarity to the loop as shown in the

side figure.

The two other contacts are used for

connecting external LED(BS-572).

This

connection

also

demands

polarity.

IN

IN

OUT

O

U

T

R

Connection with

(-L) of the loop

Connection

with external

LED

Connection with

(+L) of the loop

Mounting points

R

+

The LED goes off when we RESET the panel.

Each detector has an address with which it is

recognized from the panel.

It`s forbidden for two devices with same

addresses to be connect to the same loop.

The back page contains all the available

address settings which are done using the

dipswitch.