5
Installation and start-up
Door operator control module KNX A3-B2
• Version: 17.12.2019 • Technical changes and errors reserved.
2.2.2. Connection/ layout of the circuit board
CAUTION!
Unprotected live components!
The voltage connected to the switching outputs must conform with the
SELV spezifications (safety extra-low voltage)!
Connect the bus cable (red/black clamp).
Use the 8-wire connection line to connect the outputs and the 4-wire line to connect the
binary inputs. The lines may be extended to up to 5 m.
Outputs
Binary inputs
Programming button
Programming LED
KNX bus clamp
Fig. 1
(connector for
4-wire line)
(connector for 8-wire line)
Fig. 2
8-wire connection line for outputs:
Connection of the outputs independent from polarity.
blue
output 3
black
output 3
violet
(not connected)
black
output 2
yellow
output 2
black
(not connected)
white
output 1
black
output 1