Setting parameters
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
If the setpoint is set via parameters:
Set the setpoint for heating and/or cooling.
If the setpoint is set via communication object:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
Activation object value
before first call
0 • 1
Specified setpoint using
Parameter • Communication object
Specified setpoint using
Parameter
Setpoint heating in 0.1°C
(if the heating regulator is being used)
-300 … 800; 180
Setpoint cooling in 0.1°C
(if the cooling regulator is being used)
-300 … 800; 260
Specified setpoint using
Communication object
The last communicated value should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for
first commissioning)
Start setpoint heating in 0.1°C
valid until first call
(if the heating regulator is being used and
only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800
Limitation of object value H(min)\r\n
in 0.1°C
-300 … 800
Limitation of object value H(max)\r\n
in 0.1°C
-300 … 800
Start setpoint cooling in 0.1°C
valid until first call
(if the cooling regulator is being used and
only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800
Limitation of object value C(min)\r\n
in 0.1°C
-300 … 800
Limitation of object value C(max)\r\n
in 0.1°C
-300 … 800
Type of setpoint change
• Absolute value
• Increase / Decrease
Interval
(only when "increasing/decreasing")
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
2°C • 3°C • 4°C • 5°C