8
Transfer protocol
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
25
Temp. controller: Switching object (0:Heat-
ing | 1:Cooling)
Input
1,002
C W
26
Temp. controller: Current setpoint
Output
9,001
C R T
27
Temp. controller: Blocking object
Input
1,006
C W
28
Temp. controller: Setpoint, daytime
Heating
Input / Output
9,001
C R W T U
29
Temp. controller: Setpoint, daytime
Heating (1:+ | 0:-)
Input
1,002
C W
30
Temp. controller: Setpoint, daytime
Cooling
Input / Output
9,001
C R W T U
31
Temp. controller: Setpoint, daytime
Cooling (1:+ | 0:-)
Input
1,002
C W
32
Temp. controller: Control variable, heating
(level 1)
Output
5,001
C R T
33
Temp. controller: Control variable, heating
(level 2)
Output
5,001
C R T
34
Temp. controller: Control variable, heating
(level 2)
Output
1,001
C R T
35
Temp. controller: Control variable, cool-
ing (Level 1)
Output
5,001
C R T
36
Temp. controller: Control variable, cool-
ing (level 2)
Output
5,001
C R T
37
Temp. controller: Control variable, cool-
ing (level 2)
Output
1,001
C R T
38
Temp. controller: Night-time reduction
activation
Input
1,003
C W
39
Temp. controller: Heating setpoint, night
Input / Output
9,001
C R W T U
40
Temp. controller: Heating setpoint, night
(1:+ | 0:-)
Input
1,002
C W
41
Temp. controller: Cooling setpoint, night
Input / Output
9,001
C R W T U
42
Temp. controller: Cooling setpoint, night
(1:+ | 0:-)
Input
1,002
C W
43
Temp. controller: Heating 1 (1=ON |
0=OFF)
Output
1,001
C R T
44
Temp. controller: Heating 2 (1=ON |
0=OFF)
Output
1,001
C R T
45
Temp. controller: Cooling 1 status (1=ON |
0=OFF)
Output
1,001
C R T
46
Temp. controller: Cooling 2 status (1=ON |
0=OFF)
Output
1,001
C R T
47
Temp. controller: Window status
(0: CLOSED | 1: OPEN)
Input
1,019
C W
No.
Name
Function
DPT
Flags