12
Setting parameters
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
During initial commissioning, a threshold value must be defined which will be valid un-
til the first call with a new threshold value. For units which have already been taken into
service, the last communicated threshold value can be used. Basically, a temperature
range is given in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in EEPROM, so that this is retained in the event of a power sup-
ply failure and will be available once the power supply is restored.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Blocking
The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.
Threshold value setpoint using
Parameter •
Communication objects
The last communicated value should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming
Start threshold value in 0.1°C
valid until first call
-300 … 800; 200
Type of threshold value change
Absolute value • Increase/decrease
Interval
(upon increase/decrease change)
0.1°C • ... • 1°C • ... • 5°C
Hysteresis of the threshold value in %
0 … 50; 20
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - Hyst. below = 0
• TV above = 0 | TV - Hyst. below = 1
• TV below = 1 |TV + hysteresis above = 0
• TV below = 0 |TV + hysteresis above = 1
Switching delay from 0 to 1
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send switching output in the cycle of
(is sent only if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release