11
Setting parameters
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired.
Note:
If an external portion is used, all of the following settings (threshold values, etc.)
are related to the overall reading!
The
minimum and maximum readings
can be saved and sent to the bus. Use the
"Reset temperature (and/or humidity) min./max. value" objects to reset the values to
the current readings.
The values are not retained after a reset.
6.4.
Temperature threshold values
Activate the threshold values that you want to use here. The
Temperature Sensor
KNX T-AP
provides four threshold values.
6.4.1. Temperature threshold values 1, 2, 3, 4
Threshold value
Set the threshold values directly in the application program using parameters, or de-
fine them via the bus using a communication object.
Threshold value setpoint using parameter:
Set the threshold values and hysteresis directly.
Threshold value setpoint using a communication object:
Beforehand, enter how the threshold value will be received from the bus. Basically, a
new value can be received, or simply a command to increase or decrease.
Use external reading
Yes • No
Ext. Measured value portion of the total
reading
5% • 10% • ... • 50% • ... • 100%
Send internal and total reading
• do not send
• send periodically
• send on change
• send on change and periodically
On change of
(if sent on change)
2% • 5% • 10% • 25% • 50%
Send cycle
(if sent periodically)
5 s • ... • 2 h
Use min. and max. values
Yes • No
Use threshold value 1/2/3/4
Yes • No
Threshold value setpoint using
Parameter
• Communication objects
Threshold value in 0.1°C
-300 … 800; 200
Hysteresis of the threshold value in %
0 … 50; 20