3
Description
Ventilation Unit WL800
• Version: 28.04.2016 • Errors and technical modifications subject to change without notice.
1.0.1. Scope of delivery
•
Mounting panel with ventilation unit and 10 m connection cable for voltage
supply
1.1. Technical specification
The product is compliant with the provisions of EU guidelines.
1.1.1. Air intake opening
Sufficient sizing of the air intake opening is an important functional and comfort factor
when utilizing motorised ventilation units. If the air intake opening size falls below the
minimal size (18,360 mm² or approx. 184 cm²), reduced air performance as well as
draught and flow noises can be the result. Comfortable ventilation is achieved with an
opening size starting at 38,400 mm² (384 cm²) for each WL800.
Voltage
230 VAC, 50 Hz
Cable length
Voltage Supply
10 m
Power consumption in
exhaust mode
minimal speed: approx. 8 W
maximal speed: approx. 124 W
Radio frequency
868.2 MHz
Net air output
Exhaust air: max. approx. 555 m³/h,
Circulation air: max. approx. 163 m³/h
(For exact measuring criteria please inquire at Elsner
Elektronik)
Required air intake opening
minimum 18,360 mm² (approx. 184 cm²)
Please observe the instructions in chapter
Sound pressure
at a distance of 3 m
Exhaust mode:
approx. 37.2 dB(A) at medium speed
approx. 47.0 dB(A) at maximum speed
Circulation mode:
approx. 41.3 dB(A) at medium speed
approx. 54.1 dB(A) at maximum speed
Heat transition coefficient
0.9 W/m²K (Fan including standard panel)
Panel insulation density
60 kg
Panel compressive strength
350 kPa
Inclination
for mounting
0° (flat roof) to 90° (wall mounting)
• In case of wall mounting (from 70° to 90°), the addi-
tional option "wall device" must be ordered (sur-
charge).
• In case of flat roof mounting, water on the panel must
not exceed the height of 2 cm.