Menu 6.1 – Lock / Brake Output Modes
The relay output in the lock / brake mode can be configured in different ways.
Menu No.
Lock / Brake Modes
Factory
Default
Adjustable
6.1.1
Open Lock / Brake Activation
2 seconds
1 – 30 seconds
or hold
6.1.2
Close Lock / Brake Activation
Off
1 – 30 seconds
or hold
6.1.3
Open Pre-Lock / Brake Activation
Off
1 – 30 seconds
6.1.4
Close Pre-Lock / Brake Activation
Off
1 – 30 seconds
6.1.5
Exit
6.1.1 Open Lock / Brake Activation
This sets the time the output is activated in the
open direction. Factory default is 2 seconds.
Setting it to Hold means the output is activated for
the total travel time in the open direction.
6.1.2 Close Lock / Brake Activation
This sets the time the output is activated in the
close direction. Factory default is off. Setting it
to Hold means the output is activated for the total
travel time in the close direction.
6.1.3 Open Pre-Lock / Brake Activation
This sets the time the output is activated before
the motor starts in the open direction. Factory
default is Off.
6.1.4 Close Pre-Lock / Brake Activation
This sets the time the output is activated before
the motor starts in the close direction. Factory
default is Off.
Menu 6 – Relay Output Modes
19