background image

Technical Manual TAR x700-2

page 3

 Functional Description

Signal Input

The controller unit is able to work with the tempe-

rature sensor types TF 201 and TF 501 (Pt1000). 

This must be preset by parameter 

P25

 

Ranges

:

 

P25 = 1 (TF 201).......-50...+100°C

 

P25 = 3 (TF 501/Pt1000).......-100...+300°C

 

Please note the specific temperature restric- 

 

tions of the different sensor types (e.g.  

 

-40...+80°C with standard-TF-types) and ask  

 

for matching products if necessary.

Actual Value- and Status Display

Temperature values can be displayed in °C or °F. This 

will be preset together with the sensor type. 

P01

 shows the measured value of sensor 1. 

If other parameters are selected, 4 minutes after 

the last keypress the display switches back to P01 

automatically. In operating mode 3+4, 

P02

 shows  

the measured value of sensor 2. In operating mode 

'Differential  control', 

P03

  shows  additionally  the 

differential value between sensor 1 and 2.

Display Correction

The Actual Value Display 

P01 

can be calibrated by 

P23,

 

P02 

can be calibrated by 

P24

.

Operating Modes

The  TAR  controller  knows  4  different  operating 

modes, which can be preset by 

P19

:

 

P19 = 1:

 

3  Alarm

In  this  mode 

you realize a 3-

stage  controller, 

relay  K4  works 

as  a  closed  cir-

cuit alarm relay, 

sensor input 2 is 

disabled.

The  value  of 

sensor 1 will be 

compared  with 

P04,  P05

  and 

P06

, the relays K1, K2 or K3 switch depending on 

the deviation. P04 is always an absolute value, the 

following setpoints can be either relative values or 

absolute values (preset by 

P08

).

Relative  values  =  Stage  switches  in  a  specific 

distance to the leading setpoint P04. If P04 will be 

changed, the relative setpoints will be changed the 

same amount.

 

P19 = 2 :

 

4-stage controller

Sensor  input 

2  is  disabled 

in  this  mode. 

The  value  of 

sensor 1 will be 

compared  with 

P04,  P05,  P06 

and

  P07

,  the 

relays  K1,  K2, 

K3 or K4 switch 

depending  on 

the  deviation. 

Control setpoint 1 (P04) is always an absolute value, 

the following setpoints can be either relative values 

or absolute values (preset by 

P08

). 

 

 

P19 = 3 :

 

Double 2-Stage Controller

Sensor  1  af-

fects  on  the 

control  set-

points 

P04/

P05 

(=  relays 

K1/K2 = control 

circuit 1).

P04 is the lea-

ding setpoint of 

control  circuit 

1,  control  set-

point  2  (P05) 

can be either absolute or relative (

P08

). Sensor 2 

affects on the control setpoints 

P06/P07

 (= relays 

K3-K4 = control circuit 2). P06 is the leading setpoint 

of control circuit 2, P07 can be either absolute or 

relative (

P08

).

 

P19 = 4

 

Differential Controller

The calculated dif-

ferential  amount 

from  "sensor  1 

minus

 sensor 2" 

will be compared 

with 

P04

.

Relay  K1  swit-

ches,  if  the  pre-

set  value 

P04

  + 

hysteresis 

P18 

is  reached.  The 

relay switches off 

again,  if  the  dif-

ferential  amount 

decreases and reaches P04. The stages 2 (

relay 

K2, P05, assigned to sensor 1

) and 3 (

relay K3, 

P06, assigned to sensor 2

), can work independly 

as single stage controllers. 

Relay K4 works as a closed circuit alarm relay.

Switching Hysteresis

With 

P18

  you  set  a  switching  hysteresis,  which 

affects to all setpoints. The position of this hyste-

resis (above/below the setpoint) depends on the 

selected  switching  characteristics  (

P10

-

P13

)  of 

the single relays.

Setpoint Limits

To prevent that the final user adjusts the setpoints 

to an inadmissible value, the setpoint range can be 

limited by 

P16

 and 

P17

.

Real time clock

The integrated real time clock allows to change the 

setpoints at specific times. The timer has a power 

backup for about 10 days in case of power failure. 

The time of the day and the date can be set with 

parameters 

P35

...

P36

.

Because the display has only three digits, the time 

value comes in the following format: 

Day-/Night Mode / Setpoint Offset

Initiation by real-time clock

With 

P14/P15

 you can set a period of time within 

all setpoints will be shifted by the amount of 

P09

.  

If not necessary, you can disable P14/P15 (display 

shows "

oFF

").

Initiation by Digital Input 

Digital  Input  OK  1  can  also  be  programmed  to 

activate this offset (

P29=1

). An active 2nd setpoint 

is indicated by a flashing decimal point.

Temperature Alarm

If  the  tempe-

rature  value 

measured with 

sensor  1  ex-

ceeds the ran-

ge set by  

P27

 

and 

P28

,  the 

alarm relay will 

be  activated 

after the delay 

timer 

P26

 is run 

down. 

Parameter 

P21

  shows  the  remaining  time  up  to 

an alarm. 

P28 (lower limit) is an absolute value, P27 is always 

a relative value in a distance to the actual setpoint 

1 (P04 + potential shift).

3rd Position=

minutes x 10

1st and 2nd

Position=

hours

Relay Switching Characteristic

The Switching Characteristic of the relay K1-K4 is 

defined by the parameters 

P10...P13

. The following 

characteristics are possible:

1=  Refrigeration (RF)

    Used for standard applications (e.g.    

    temperatures above 0°C). The load would be  

    switched by the N/O-contact.

    Actual value = se hysteresis: Relay on

2 =  Freezing (FR)

    The load would be switched by the N/C- 

    contact, this enables that the load will be 

    switched on permanently in case of mains 

    loss or controller defect.    

 

    Actual value = se hysteresis: Relay off

3 =  Heating (HT)

    Usable for heating applications. Load   

    would be switched off in case of mains  

    fail or controller defect.  

 

    Actual value = setpoint 

-

 hysteresis: Relay on

Minimum Idle-Time

If a load is switched off by a relay, this relay cannot 

be switched on again before the time set with 

P20

 

is over. P20 affects all relay stages. 

The indicator LED's of the single stages flashes 

while this idle time runs. 
The Minimum Idle-Time affects immediately after 

power-on of the controller.

  Digital Input

Digital input DI1 is normally connected to mains 

voltage. If this voltage is interrupted, the function set 

with 

P29

 will be initiated after a time delay (

P30

).

 

P30

 is adjustable within 0...99 minutes, but at '0' the 

minimum delay is appr. 4 seconds.

P29=oFF  Digital input DI/OK 1 is de-activated
P29=1 

Control Setpoint 2

 (night-setpoint) is  

 

 

active. The setpoints increase/  

 

 

decrease by the amount of P09.

P29=2 

An 

external alarm

 is detected after  

 

 

P30 is run down. LED 4 and the alarm  

 

 

relay are activated after P26 has been  

 

 

run down.

P29=3 

Controller unit oFF

. All control  

 

 

functions will be disabled, the display  

 

 

shows "oFF". This allows to switch off  

 

 

the unit without an alarm message in  

 

 

a network. Relays 1-3 are deactivated,  

 

 

the alarm relay remains in a neutral  

 

 

position.

 

 

Analogue output behaviour:

 

 

• Delivers 0V with op-mode 

 

 

  proportional (P34=1 or 3). 

 

 

• Delivers 10V with op-mode

 

 

  anti-proportional (P34 = 2 or 4)

P22

 shows the remaining delay time of the digital 

input.

Using the 

TAR 1700-2

 this function must 

be started by opening an external, potential 

free contact connected to terminals 11/12. 

Never connect mains voltage to these 

terminals, danger of destruction! 

This 

contact must be suitable for 5VDC/1mA.

K4

K3

P06

K2

P05

sens2

sens1

K1

P04

K4

K3

P07

P06

K2

P05

sens2

P04

K1

sens1

K2

P05

K4

K3

P06

P07

sens2

control circuit 1

control circuit 2

sens1

K1

P04

K4

K3

P06

K2

P05

sens2

K1

P04

Diff.

sens1

alarm after P26 is run down

alarm after P26 is run down

tem

per

atu

re p

rofi

le

Upper AT

P27

(relative)

Lower AT

P28

(absolute)

Отзывы: