background image

page 6

Technical Manual TAR x700-2

 CONNECTION INFORMATION & SAFETY INSTRUCTIONS

The guarantee will lapse in case of damage caused by failure 

to comply with these operating instructions! We shall not be 

liable for any consequent loss! We do not accept liability for 

personal injury or damage to property caused by inadequate 

handling or non-observance of the safety instructions! 

The guarantee will lapse in such cases. 

 

This manual contains additional safety instructions in the  

 

functional description. Please note them!

If you notice any damage, the product may not be connected 

to mains voltage! Danger of Life!

A riskless operation is impossible if:

• The device has visible damages or doesn't work

• After a long-time storage under unfavourable conditions

• The device is strongly draggled or wet

• After inadequate shipping conditions
• Never use this product in equipment or systems that are  

  intended to be used under such circumstances that may  

  affect human life. For applications requiring extremely  

  high reliability, please contact the manufacturer first.
• 

The product may only be used for the applications  

  described on page 1.
•  Electrical installation and putting into service must be  

  done from qualified personnel. 

• 

 During installation and wiring never work when the 

  electricity is not cut-off ! Danger of electric shock!

• 

 Never operate unit without housing. 

  Danger of electric shock!

•  

All ‘PE’ terminals must be connected to ground.  

  Danger of electric shock! 

Additionally, the internal noise  

  filter will not work, faulty indicated values may occur.
•  Please note the safety instructions and standards of your  

  place of installation!

•  Before installation: Check the limits of the controller and    

  the application (see tech. data). Check amongst others:

  - Make sure that all wiring has been made in accordance    

    with the wiring diagram in this manual.

  - Supply voltage (is printed on the type label).

  - Environmental limits for temperature/humidity. 

  -  Maximum admitted current rate for the relays. Compare    

    it with the peak start-up currents of the controlled loads   

    (motors, heaters,etc.). 

 

    Outside these limits malfunction or damages may occur.
•  Sensor/probe cables must be shielded. Don’t install them    

  in parallel to high-current cables. Shielding must be  

 

  connected to PE at the end close to the controller. 

  If not, inductive interferences may occur. 
•  Please note for elongation: The wire gauge is not critical,    

  but should have 0,5mm² as a minimum.
•  Mounting the controller close to power relays is    

 

  unfavourable. Strong electro-magnetic interference,  

 

  malfunction may occur!
•  Take care that the wiring of interface lines meets the  

 

  necessary requirements.
• All used temperature sensors must be identical. Never    

  use different types at the same time. This will not work.
•  TF-type sensors are not designed for being immersed in    

  fluids permanently. In such a case, always use dip-fittings.   

  With extreme temperature variations, the sensor may be    

  damaged.

Cleaning

 

The use of a dry, lint-free cloth and household agents is sufficient 

to clean the product. 

Never use acids or acidic fluids!  Risk of damage!

 Installation / Start-up

Read Safety Instructions !

If the TAR unit is switched ON, the display shows 

the actual value of sensor 1. At first you have to set 

the basic parameters:

• 

Enter Access Code '70' at P41

• 

Operating mode (P19)

• 

Type of used sensor (P25)

• 

Enter Access Code '88' at P40

• 

Switching characteristic of the relays 

 

(P10-P13)

• 

Task of control input DI1 (OK1) (P29)

• 

If the unit is networked: 

 

Address in network (P39) and Baudrate (P38)

• 

Function of the Analogue Output (P31 - P34)

This was the basic configuration, now you can enter 

the specific setpoints, times, etc.

Installation hint:

If the measured values 'jump' check the 

following: Is the shielding of the sensor 

wire connected to PE near the controller 

unit? Is the PE terminal of the controller 

unit connected to PE? If the sensor wire 

is shielded correctly but the value on the 

display continues 'jumping', please try 

to solve the problem by removing the 

shield from PE and connecting it to a 

ground terminal of the TAR.

Display Adjust

To calibrate the two actual value displays, use para-

meters 

P23

 resp. 

P24

 to correct the value. 

original set up:  9.3.18, tkd/jr 

checked:  12.3.2018, ek/ha  approved:  12.3.2018, mv/mh  transl.():  

corr: 

For the devices 

TAR 1700-2, TAR 3700-2 and TAR 5700-2 we state the following: 

When operated in accordance with the technical manual, the criteria have been met that are outlined in the EMC Directive 

2014/30/EC and the Low Voltage 

Directive 

2014/35/EC. This declaration is valid for those products covered by the technical manual which itself is part of the declaration.

Following standards were consulted for the conformity testing to meet the requirements of EMC and Low Voltage Guidelines:

EN 55011:2016, EN 61010-1:2010, EN 61326-1:2013  

CE marking of year: 2017

This statement is made for the manufacturer / importer 

 

by: 

ELREHA Elektronische Regelungen GmbH 

 

Werner Roemer,

Technical Director 

D-68766 Hockenheim

 

    

www.elreha.de  

Hockenheim

......

12.6.2017

.................................................................

(

Name / Address

)

C

ity                              Date

          S

ignature

EC Declaration of Conformity

Отзывы: