Parameter Page MiniMEP (2)434 A/ (2)534 A
, Temperature-/Humidity Recording.
(Default values are factory set)
Parameter name
Description
Range
Default value
Your value
serial number
individual serial number for clear idenfication of the unit
--
--
software
version no. of the so additional info
Add. info: "pro" = unit is unlocked for use with "CV-Scheduler"
MiniMEP
shows type of unit, quantity and kind of probe inputs
recording
storage interval in minutes
1...6,10,12,15,20,30,60 min. 5 min.
unit
physical unit of all temperature values
°C(elsius), °F(ahrenh.)
°C
(°F always in 0,2°F steps)
(transm 1) corr. 1
the last four corrections of this input with time,
-6% bis +6%
0%
to
date and offset value
(transm 1) corr. 4
(transm 1) on/off
if you don't want to use input 1, switch it off here
off / on
on
transm 1 L-Limit
humidity low limit transmitter 1
0,0% ... 100,0%
0%
transm 1 H-Limit
humidity high limit transmitter 1
0,0% ... 100,0%
100%
transm 1 delay
if this delay is run down, an alarm message will be generated 0:01 ... 4:00 h:min
1:00 h:min
name transm 1
individual name for this probe input (max. 8 characters)
see table
transmitter 1
(probe 2) corr. 1
the last four corrections of this input with time,
to
date and offset value
(probe 2) corr. 4
(probe 2) on/off
if you don't want to use probe 2, switch it off here
off / on
off
probe 2 L-Limit
undertemperature setpoint probe 2
-160..+850°C/-256..+1562°F -160°C (-256°F)
probe 2 H-Limit
overtemperature setpoint probe 2
-160..+850°C/-256..+1562°F +850°C (+1562°F)
(-256...+1562°F)
probe 2 delay
if this delay is run down, an alarm message will be generated 0:01 ... 4:00 h:min
1:00 h:min
name probe 2
individual name for this probe input (max. 8 characters)
see table
probe 2
(transm 3) corr. 1
the last four corrections of this input with time,
-6% bis +6%
0%
to
date and offset value
(transm 3) corr. 4
(transm 3) on/off
if you don't want to use input 3, switch it off here
off / on
off
transm 3 L-Limit
humidity low limit transmitter 3
0,0% ... 100,0%
0%
transm 3 H-Limit
humidity high limit transmitter 3
0,0% ... 100,0%
100%
transm 3 delay
if this delay is run down, an alarm message will be generated 0:01 ... 4:00 h:min
1:00 h:min
name transm 3
individual name for this probe input (max. 8 characters)
see table
transmitter 3
(probe 4) corr. 1
the last four corrections of this input with time,
to
date and offset value
(probe 4) corr. 4
(probe 4) on/off
if you don't want to use probe 4, switch it off here
off / on
off
probe 4 L-Limit
undertemperature setpoint probe 4
-160..+850°C/-256..+1562°F -160°C (-256°F)
probe 4 H-Limit
overtemperature setpoint probe 4
-160..+850°C/-256..+1562°F +850°C (+1562°F)
probe 4 delay
if this delay is run down, an alarm message will be generated 0:01 ... 4:00 h:min
1:00 h:min
name probe 4
individual name for this probe input (max. 8 characters)
see table
probe 4
alarm repeat
alarm repetition time after a reset with a failure still present
off, 0:01 ... 4:00 h:min
off
accu alarm mess.
accu alarm message if mains voltage fails
on, off
on
DI alarm w. accu
alarms from digital inputs allowed while accu operation
on, off
on
(digital inputs)
here the digital inputs can be switched on or off
al1 al2 door
off off off
1(al1) 2(al2) 3(door)
off off off
........to........
on on on
delay door
time delay for digital input #3
0:00 ... 4:00 h:min
0:00 h:min
L/inp. 3 (door)
individual name for digital input #3
see table
door
delay al2
time delay for digital input #2
0:00 ... 4:00 h:min
0:00 h:min
L/inp. 2 (al2)
individual name for digital input #2
see table
al2
delay al1
time delay for digital input #1
0:00 ... 4:00 h:min
0:00 h:min
L/inp. 1 (al1)
individual name for digital input #1
see table
al1
actual time
can be correctedround about 90 minutes only
h:min:sec
factory set
actual date
cannot be corrected
factory set
summer/winter
regulation for the summer / winter shifting
EU since '96, NO
EU since '96
actual error
"see failure codes"
last error 1
the last 6 errors
date, time, error
to
last error 6
date, time, error
DDC-baudrate
communication speed with PC-software
Baud:
9600, N ,8 ,1
1200 - 57600
begin print
date/time of the first value that should be printed out
end print
date/time of the last value that should be printed out
start with key 'arrow up', break with 'arrow down'
begin print - end print
Sprache / language
display language
german, english,
french, netherlands
adress (in network)
adress of the unit within a network
0 -78
78