Technical Manual  Humidity Controller EVP 3260

Page  6

Control via Dual Setpoint Controller

The EVP 3260 is a Dual Setpoint Controller for humidity with an upper set-

point for dehumidify and a lower setpoint for humidification, each with an own 

hysteresis.

Switching points:

Dehumidify

Switching point  Actual value ≥ Setpoint dehu Hysteresis dehumidify

Off point  

Actual value < Setpoint dehumidify

Humidification

Off point  

Actual value > Setpoint humidification

Switching point  Actual value ≤ Setpoint humidification - Hysteresis humidif.

The setpoint 'Setpoint dehumidify' is used for cooling resp. dehumidification, 

the setpoint 'Setpoint humidification' is used for heating resp. humidification.

   

Setpoints and hysteresis can be set in the way, that the switch-on    

   

points can never not be reached possibly. 

   

To draw attention to this critical attitude, at this conditions an 

   

assigment failure appears:

   

 

Setpoint dehu Hysteresis dehumidify > 100,0%

   

 

Setpoint humidification - Hysteresis humidification < 0,0%

Control via Analogue Output

To the analogue output the actuating variable of a PI controller with 'dead time 

compensation' can be switched. The necessary parameters (setpoint, propor-

tional range, delay time, interval, step-width) are working independent from the 

dual  setpoint controller.

Alarm Limits

Absolute alarm limits 'alarm limit dehumidify' and 'alarm limits humidification' 

are available. The hysteresis for them is fixed to 1,0% and can not be adjusted. 

At dehumidify the hysteresis is below and at humidification above the alarm 

setpoint:

  Alarm dehumidify ON:  

Actual value > Alarm limit dehumidify

  Alarm dehumidify OFF:  

Actual value ≤ Alarm limit dehumidify - 1,0% 

   

 

(but min. 0,0%)

  Alarm humidification OFF: 

Actual value ≥ Alarm limit humidifi 1,0%

   

 

(but max. 100,0%)

  Alarm humidification ON:  

Actual value < Alarm limit humidification

The parameter 'Alarm delay dehumidify' is deactivated, if the alarm limit is set to 

100,0%. The parameter 'Alarm delay humidification' is deactivated if the alarm 

limit is set to 0,0%.

For both alarm setpoints an individual alarm delay is available. The alarms 

have no influence on the control function.

Night Operation

For a night operation a second setpoint set for setpoints and alarm limits is 

available. The hysteresis 'Hysteresis dehumidify' and 'Hysteresis humidifica-

tion' will be shared for day/night operation.

Current Failures

The following current failures are possible:

1. Sensor failure

2. Assignment failure

3. Hardware failure

4. Alarm dehumidify and alarm humidification
The failure messages of the failures after 1-3 appear after a fixed delay in a 

second range.

The failure messages of the failures after 4 appear after the set alarm delay 

time. All current failures can be read at the parameter 'Current Failure' and can 

also retrieved via the data interface. If a failure appears, the display shows the 

current failure and starts flashing.

Assignment Failure

In the following cases an assignment failure will be released:

▪  

Alarm limit dehumidify < Setpoint dehu Hysteresis dehumidify

▪   Alarm limit humidification > Setp. humidification - Hysteresis humidification

▪   Night 

alarm limit dehumidify < Night setp. dehum. + Hysteresis dehumidify

▪   Night alarm limit humidification > Night setp. hum. - Hysteresis humidification

▪   Setpoint dehumidify ≤ Setpoint humidification

▪   Night setpoint dehumidify ≤ Night setpoint humidification

▪   Setpoint dehu Hysteresis dehumidify > 100,0%

▪   Setpoint humidification - Hysteresis humidification < 0,0%

▪   Non supported / faulty ressource assignments

Historic Failures

Always the last 15 failure messages will be stored in the controller. This historic 

messages are accessible only via the interface.

Compound Functions

If the EVP is connected to a compound system, it can be assigned to com-

pound 1, 2, 3 or no compound.

If a compound assignment is set, the function 'control dehumidify' can be swit-

ched oFF by the VPR-System with a plant failure or for 'Low Power Optimiza-

tion' of the corresponding compound.

However, the 'setpoint humidification' can only be switched off with a set com-

pound assignment and with a plant failure of the compound.

Sensors and Sensor Corrections

Entered correction values will be added to the actual values and limited to the 

valid range of values within 0,0%…100,0%.

  If actual value + correction < 0,0%   →   0,0%

  If actual value + correction > 100,0%  →   100,0%

Interface / Data Connection

All actual values and parameters of the unit can be read and adjusted via the 

data interface. Independently from the display resolution % values will be trans-

mitted as 0.1% values.

Remote Display

At the EVP 3160, the connection of remote displays of the series TAA xx15 is 

possible. This displays are able to display optionally the actual values '

L01

', 

'

L05

' and '

L06

'. 

The connection at the controller can be done exclusively via the RS-485 inter-

face at the terminals 20 and 21. 

Multiple TAA xx15 can be connected via this interface, in this case each display 

is able to display the same or different actual values.

At the EVP not settings are necessary. The selection of the actual values must 

be done via the address switch at the remote display, address 1, 5 and 6 for the 

parameters L01, L05 and L06. 

The values on the remote display appear with the same resolution as at the 

EVP. 

Functions

Info

 Real Time Clock

The built-in real time clock has a buffer for max. 10 

days without mains voltage. Date and time can be 

set by "

P80

"..."

P85

" (Mode Page). 

By default, a GMT +01:00 is set ("Time Zone Offset" = 

60 min.), which is standard for the Central European 

Space. If the product is used in other countries, this 

value can be changed.
Summer/Winter Switch - Time Zones

An automatic summer/winter switch "

P70 

= EU" 

(Mode Page) considers the current EU-rules from 

1996 (EU 96), but can also be switched off or set 

as needed.

 

Variable Time Zones

The  function  for  Variable  Time  Zones  can  be 

activated by "

P70 

= tun" and is adaptable by the 

parameters "

P72

"..."

P79

". 

P72

 

(SummerON Month) 

(Fact.Setting March, 3rd)

  The month of the beginning of the summertime

P73

 

(SummerON Day)

 ...(Fact.Setting. 0, sunday)

  The weekday of the beginning of the summert.

P74

 

(SummerON x-Day)

 ...(Fact.S. 5, last sunday)

  The x-th with "

SummerON Day

" preset day of  ..

  the month

P75

 

(SummerON Hour)

 ..... (Fact.Set. 2, 2 o'clock)

  The hour of the beginning of the summertime

P76

 

(SummerOFF Month)

 (Fact.Set. October, 10th.)

  The month of the end of the summertime

P77

 

(SummerOFF Day)

 ...(Fact.Setting 0, sunday)

  The weekday of the end of the summertime

P78

 

(SummerOFF x-Day)  ..

(Fact.S. 5, last sunday)

  The x-th with "

SommerOFF Day

" preset day of  

  the month

P79

 

(SummerOFF Hour)

 .. (Fact. Set. 3, 3 o'clock)

  The hour of the end of the summertime
The shift to the summer resp. winter time is set by 

the time setting which is active at this time

.

Содержание EVP 3260

Страница 1: ...int Page P Mode Page h Assign ment Page L01 r01 P01 h01 1 Parameter on the P P P Access Protection Except the temperature setpoints parameters can be changed only after entering a correct access code...

Страница 2: ...After a long time storage under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to...

Страница 3: ...the controller the display will indicate the permanent parameter after some seconds or in case of a failure it will display the current failure This can also be read if you don t touch a key for more...

Страница 4: ...oFF switched off from the VPR 0 1 off L43 X Day Night Mode 0 day 1 night 0 1 L44 X Operation state of the controller on off L50 X Current value of the analogue output in X of the selected range 0 100...

Страница 5: ...ht operation active low dnK night operation active high ofl unit oFF active low ofK unit oFF active high tol dehumidifiy oFF active low toK dehumidifiy oFF active high bol humidification oFF active lo...

Страница 6: ...resis humidification Setpoint dehumidify Setpoint humidification Night setpoint dehumidify Night setpoint humidification Setpoint dehumidify Hysteresis dehumidify 100 0 Setpoint humidification Hystere...

Страница 7: ...ity Dimensions Connection 1 2 3 4 1 2 8 3 4 5 7 6 12 11 9 13 10 22 EVP 20 21 27 23 24 25 26 28 32 29 31 30 105 4 13 46 1 81 63 2 48 91 3 58 115 4 53 19 15 18 14 16 17 ELREHA P 38 37 34 33 35 36 analog...