Technical Manual  Humidity Controller EVP 3260

Page 4

 Parameter Pages

Actual Values Page  

(L) 

Param. 

  

Note 

 

Range 

Factory Setting

r01

  .........................Day setpoint dehumidify ............................................................................................................0,0...100,0 % ............... 70,0 %

r02

  .........................Day setpoint humidification  ......................................................................................................0,0...100,0 % ............... 50,0 % 

r03

  .........................Day alarm limit dehumidify ........................................................................................................0,0...100,0 % ............... 100,0 %

r04

  .........................Day alarm limit humidification ...................................................................................................0,0...100,0 % ............... 0,0 %

r11

  .........................Night setpoint dehumidify  .........................................................................................................0,0...100,0 % ............... 70,0 %

r12

  .........................Night setpoint humidification  ....................................................................................................0,0...100,0 % ............... 50,0 % 

r13

  .........................Night alarm limit dehumidify ......................................................................................................0,0...100,0 % ............... 100,0 %

r14

  .........................Night alarm limit humidification .................................................................................................0,0...100,0 % ............... 0,0 %

r21

  .........................Hysteresis dehumidify ...............................................................................................................0,1...20,0 % ................. 5,0 %

r22

  .........................Hysteresis humidification ...........................................................................................................0,1...20,0 % ................. 5,0 %

r31

  .........................Alarm delay dehumidify .............................................................................................................0...120 min.  ................. 45 min.

r32

  .........................Alarm delay humidification ........................................................................................................0...120 min.  ................. 45 min.

r51

  .........................Min. idle time dehumidify ...........................................................................................................0...30 min.  ................... 0 min.

r52

  .........................Min. idle time humidification  .....................................................................................................0...30 min. .................... 0 min.

r61

  .........................PI - setpoint day .........................................................................................................................0,1...100,0 % ............... 50,0 %

r62

  .........................PI - setpoint night .......................................................................................................................0,1...100,0 % ............... 50,0 %

r63

  .........................PI - proportional range ...............................................................................................................0,1...30,0 % ................. 5,0 %

r64

  .........................PI - delay time ............................................................................................................................

off

, 1...600 sec.  ......... 10 sec.

r71

  .........................PI analogue output, output delay ..............................................................................................0...240 sec. .................. 0 sec.

r72

  .........................PI analogue output, step width ..................................................................................................1...100% ...................... 100%

r73

  .........................Pulse duration for relay humidification/dehumidify ...................................................................1...240 sec ................... 1 sec.

r74

  .........................Switch on time pulse/relay humidification/dehumidify ..............................................................1...240 sec. .................. 240 sec.

Setpoint Page 

(r)

 

Param.    Disp   Note 

 

Range 

Factory Setting

L01

  ..............X .........Actual humidity value at sensor 1  .......................................................................................................0...+100% r.H.  ........... ---

      

 

(All inputs are correctable in the mode page, functions are selected in the assignement page)

L05

  ..............X .........Actual humidity value at sensor 5 ............................................................................................. 0...+100% r.H. ............ ---   

 

L06

  ..............X .........Actual humidity value at sensor 6 ............................................................................................. 0...+100% r.H. ............ ---

L20

  ..............X .........Current Failure ............................................................................................................................................................... ---

L36

  ..............X .........Remaining min. idle time dehumidify ........................................................................................ minutes

L37

  ..............X .........Remaining min. idle time humidification ................................................................................... minutes

L41

  ..............X .........Dehumidify control (0 = off, 1 = on, oFF = switched off from the VPR) ...................................

0, 1, off

L43

  ..............X .........Day/Night Mode (0 = day, 1 = night) .........................................................................................

0, 1

L44

  ..............X .........Operation state of the controller ...............................................................................................

on, off

L50

  ..............X .........Current value of the analogue output in X% of the selected range ......................................... 0-100%

L60

  ..............X .........States of the digital inputs DI 1 and DI 2 ..................................................................................

L61

  ..............X .........States of the relays 1-3 .............................................................................................................

Mode Page 

(P)

Param. 

  

Note 

Range 

 

Factory Setting

P01

  ..........................Assigned to compound no. (0 = not assigned) ...............................

0, 1, 2,, 3

  ..................................................................0

P21

  ..........................Night operation ON at (In 10 min. steps) .........................................00.0 ... 23.5, 

oFf

  .....................................................

oFf

 

P22

  ..........................Night operation OFF at (In 10 min. steps) .......................................00.0 ... 23.5, 

oFf

  .....................................................

oFf

P31

  ..........................Calibration of humidity sensor 1 ......................................................+/- 20,0 % adjustable ...............................................0,0 %

P35

  ..........................Calibration of humidity sensor 5 ......................................................+/- 20,0 % adjustable  ..............................................0,0 %

P36

  ..........................Calibration of humidity sensor 6 ......................................................+/- 20,0 % adjustable  ..............................................0,0 % 

 

P41

  ..........................Actual value display resolution ........................................................0 = 1%, 1 = 0,1%  ....................................................1

P51

  ..........................Analogue output delivers 0V resp. 4mA if control sensor temp.= .....0,0...100,0 % ............................................................0,0 %

P52

  ..........................Analogue output delivers 10V resp. 20mA if contr. sens. temp. = ....0,0...100,0 % ............................................................100,0 %

P70

  ..........................Standard of summer/winter switch ..................................................0 = oFF, 1 = EU, 2 = 

tVn 

(variable) ........................1

P71

 ...........................Time Zone Offset ..............................................................................-720...720 min. .........................................................60 min.

P72

 ...........................SummerON Month  ..........................................................................(only for 

tVn

) 1...12 ..................................................3

P73

 ...........................SummerON Day ...............................................................................(only for 

tVn

) 0(Sund.)...6  .......................................0

P74

 ...........................SummerON x-Day ............................................................................(only for 

tVn

) 0...5(last), 0 = off ................................5

P75

 ...........................SummerON Hour .............................................................................(only for 

tVn

) 0...23 ..................................................2

P76

 ...........................SummerOFF Month .........................................................................(only for 

tVn

) 1...12 ..................................................10

P77

 ...........................SummerOFF Day .............................................................................(only for 

tVn

) 0(Sund.)...6 ........................................0

P78

 ...........................SummerOFF x-Day ..........................................................................(only for 

tVn

) 0...5(last), 0 = off ................................5

P79

 ...........................SummerOFF Hour ...........................................................................(only for 

tVn

) 0...23 ..................................................3

P80, P81

  ..................Year, Month 

P82, P83

  ..................Day, Hour 

P84, P85

  ..................Minute, Second

P87

  ..........................Software version

P89

  ..........................Data transmission speed (Baudrate) ...............................................12(00)...115(00) ........................................................96(00)

P90

  ..........................Address of the controller unit in a network ......................................0 - 78 .........................................................................78

Parameters marked by "

Disp

" are for information only 

and cannot be changed. 

Due to the free assignment, not all parameters 

are required. 

All not required parameters will be fade out.

If this point is ON while displaying a

parameter number, the parameter is 

active at present

2

1

3

Relays

ON

OFF

DI

2

1

mains

0V

Содержание EVP 3260

Страница 1: ...int Page P Mode Page h Assign ment Page L01 r01 P01 h01 1 Parameter on the P P P Access Protection Except the temperature setpoints parameters can be changed only after entering a correct access code...

Страница 2: ...After a long time storage under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to...

Страница 3: ...the controller the display will indicate the permanent parameter after some seconds or in case of a failure it will display the current failure This can also be read if you don t touch a key for more...

Страница 4: ...oFF switched off from the VPR 0 1 off L43 X Day Night Mode 0 day 1 night 0 1 L44 X Operation state of the controller on off L50 X Current value of the analogue output in X of the selected range 0 100...

Страница 5: ...ht operation active low dnK night operation active high ofl unit oFF active low ofK unit oFF active high tol dehumidifiy oFF active low toK dehumidifiy oFF active high bol humidification oFF active lo...

Страница 6: ...resis humidification Setpoint dehumidify Setpoint humidification Night setpoint dehumidify Night setpoint humidification Setpoint dehumidify Hysteresis dehumidify 100 0 Setpoint humidification Hystere...

Страница 7: ...ity Dimensions Connection 1 2 3 4 1 2 8 3 4 5 7 6 12 11 9 13 10 22 EVP 20 21 27 23 24 25 26 28 32 29 31 30 105 4 13 46 1 81 63 2 48 91 3 58 115 4 53 19 15 18 14 16 17 ELREHA P 38 37 34 33 35 36 analog...

Отзывы: