Chapter 6
Diagnostics
MAN_105G_1.5
Page
86
1
Green
-
The Link led indicates that the module is connected to an
Ethernet network.
2
Green
Off
No power applied to module.
2
Green
Steady
Device operating correctly.
2
Green
Flashing
Module has not been configured.
2
Red
Flashing
Minor recoverable fault has been detected.
2
Red
Steady
Major internal error has been detected.
2
Green/Red
Flashing
Power on self-test.
3
Green
Off
No power applied or no IP address has been assigned.
3
Green
Steady
Module has at least one Ethernet/IP connection established.
3
Green
Flashing
No Ethernet/IP connections to the module.
3
Red
Flashing
Connection timeout
3
Red
Steady
Duplicate IP address
3
Green/Red
Flashing
Power on self-test.
4
Green
Flashing
Flashes each time a packet is received or transmitted.
6.4.2
Profibus Indicating LED’s
The module is equipped with four LED's mounted at the front and one LED on
the board, used for debugging purposes.
Led Positions are shown below.
The function of the LED's is described in the table below.
1
-
Not Used
2
Green
Module is On-Line and data exchange is possible.
2
Off
Module is not On-Line
3
Red
Module is Off-Line and no data exchange is possible.
3
Off
Module is not Off-Line
4
Flashing
Red 1 Hz
Error in configuration: IN and/or OUT length set during initialization of
the module is not equal to the length set during configuration of the
network.
4
Flashing
Red 2 Hz
Error in User Parameter data: The length/contents of the User Parameter
data set during initialization of the module is not equal to the
length/contents set during configuration of the network.
4
Flashing
Red 4 Hz
Error in initialization of the Profibus communication ASIC.
4
Off
No diagnostics present
LED no. Indication Description
2
4
1
3