background image

User Manual   

  Condor 415U-1-Cx Battery Powered Wireless IO 

Version 1.4 

  

26 

Addr: 5 
Model: 5ELPROTECH##0000011.0001 
 
 

 

 

 

 

 

 

 

 

 

MV0 

MV1 

MV2 

MV3 

MV4 

MV5 

MV6 

MV7 

ID 

Format 

F-4  

F-4  

F-4  

F-4  

F-4  

F-4  

F-4  

F-4  

Offset 

 

 

 

 

 

 

 

 

Sens 

 

 

 

 

 

 

 

 

Value 

#1.11#  #22.78#  #3.33#  #4.44#  #5.56#  #6.67#  #7.78#    #8.89# 

 

 

 

 

 

 

 

 

 

SDI SENSOR 5ELPROTECH##0000011.0001 Menu: 
        a)      MV0 

 

 

 

 

 

 

 

 

        b)      MV1 

 

 

 

 

 

 

 

 

        c)      MV2 

 

 

 

 

 

 

 

 

        d)      MV3 

 

 

 

 

 

 

 

 

        e)      MV4 

 

 

 

 

 

 

 

 

        f)      MV5 

 

 

 

 

 

 

 

 

        g)     MV6 

 

 

 

 

 

 

 

 

        h)     MV7 

 

 

 

 

 

 

 

 

       Selection:  

 

 

 

 

 

 

 

 

 
In the above example sensor, you can see that there are 8 variables reported by the SDI-12 sensor and 
can be mapped as an input to transmit in the 415U-1-Cx unit.  By default, each of these variables is 
disabled indicated by 

 in the ID row.  

You can now configure the 415U-1-Cx sensor ID to a value other than 255 to enable transmitting of 
data and then configure the sensitivity, zero/offset, display units as required for the application. 
Note that all SDI-12 measurement variables are sent as floating-point values. 
Select the letter corresponding to the measurement variable that you need to configure, and the 
menu below will be displayed to allow the setup of each individual sent DATA sensor IDs. 

MV1 
ID          30 
Value    #22.7778# 
Format  F-4 
Offset    0 
Sens       0.1 

Current configuration values 

 

 

MV2 Menu: 

 

a)      DATA Sensor ID (255 to disable) 

Configure the transmitted sensor ID. 

b)      Report Format 

For SDI-12 this is fixed as F-4 which is a float single 
precision value. 

c)      Zero / Offset 

Zero or offset adjustment value if required. 

d)      Display Units 

Engineering units to display, eg mm, ft, PSI, degC 

e)      Report Sensitivity 

Value of change before a event will be triggered and 
value is sent. 

 
 
 
 

Discrete Outputs 

Outputs Operation 

Note:  supported in R1.6 or later firmware 

Содержание CONDOR 415U-1 Series

Страница 1: ...Version 1 4 ELPRO 415U 1 Cx Condor Series Battery Powered Wireless IO Configuration Manual...

Страница 2: ...follow the instructions can cause personal injury and or property damage Proper use Any unauthorized modifications to or use of this equipment outside its specified mechanical electrical or other oper...

Страница 3: ...t generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no gua...

Страница 4: ...erview 6 Introduction 6 System Design 6 Network Design 7 Simple System Network Diagram Example 8 Large system Network Diagram Example 8 System Design Considerations 8 Ordering Guide 9 Model Overview 9...

Страница 5: ...Configuration 27 Saving and loading of Unit Configuration 29 Diagnostics 31 Diagnostic menu options 31 LED Functionality 34 OK LED Red Status Internal register bits decoder 35 Restore factory default...

Страница 6: ...from the 415U 1 Cx units in internal registers which can then be distributed to other units in the system or read by SCADA or DCS The 415U E Cx or 415U 2 Cx units can be configured as either base rep...

Страница 7: ...riod Check for association Sensor inputs Send any input values that might have changed since first send Outputs Update if configured Read each output value discrete output or analog setpoint value Fin...

Страница 8: ...ay the IO to other units in network or a SCADA DCS Commissioning considerations Check and record radio signal strength and background noise at each 415U 1 Cx unit and the AP to confirm that there is a...

Страница 9: ...Select Radio Type from Table Below BATS ERTA2 LFP Lithium iron phosphate LFP rechargeable long life 3 0AHr battery for 415U 1 Cx 905U K2 with cable and connector BATS ERTA2 LiP Lithium thionyl Chlori...

Страница 10: ...Rail horizontal or vertical mounted using an aluminium mounting plate and either Standard U clamps or s s cable ties Grounding To provide maximum surge and lightning protection for antenna connection...

Страница 11: ...y inspected when troubleshooting because the vulcanizing seal can be easily removed To obtain the maximum range collinear and dipole antennas should be mounted vertically preferably at least one wavel...

Страница 12: ...rrent loops To get the best battery life performance the ALS should be configured in the 415U 1 Cx unit to only turn on during the sample period and can also provide a sensor warmup time before sampli...

Страница 13: ...30W solar panel 12V Panel only to power or charge the internal or external Lithium battery as well as connections for the battery and Heater control External supply or Solar Connection should be conne...

Страница 14: ...ices such as printers scanners and is available from ELPRO part number CBLUSB ATOB To access the text based configuration menu through USB or RS 232 you will need a serial terminal emulator You can us...

Страница 15: ...ations Quick Start Guide Below is a QuickStart guide for connecting a 415U 1 Cx Lower Power I O radio to a 415U 2 Cx C Condor Radio Connect to the 415U 1 Cx Terminal menu and navigating to the Unit co...

Страница 16: ...ugh the Network and Radio config selections and match the parameters shown below between the 415U 2 Cx AP and the 415U 1 Cx Low Power I O Below shows the relevant Network parameters that need to be co...

Страница 17: ...store the value in at the AP A value of 0 will disable the sensor so that it does not generate update or change of state events to trigger messages to be sent over the communications network It is re...

Страница 18: ...one for multiple units using multipliers This can be used a basis for most applications and then the sensor inputs and discrete output can be tailored to fit with the application Selecting I O Quick S...

Страница 19: ...where it is not used so that no data is transmitted Below is a listing of REG address ranges that are recommended for use in a 415U E Cx or 415U 2 Cx units when used as the AP for the 415U 1 Cx unit...

Страница 20: ...tion options for each of the inputs Digital Input ON OFF Pulsed 1 Y Y 2 Y Y 3 Y Y 4 Y N Discrete input configuration Menu For each discrete digital the menu below is displayed to allow the configurati...

Страница 21: ...point value e Display Units Engineering units used for display of values inside configuration menus f Display Scaling Additional scaling for displayed engineering units g Report Sensitivity Number of...

Страница 22: ...0 Analog Set Point Menu a AN1 Set Point Configure analog input 1 setpoint registers high low default and register values b AN2 Set Point Configure analog input 1 setpoint registers high low default an...

Страница 23: ...ield values A Modbus mapping in required to be configured for each sensor input value This mapping defines the Modbus ID register address value format and the AP register address that the value will b...

Страница 24: ...as in menu below f Slave ID 2 REG 10001 FC 2 00000 AP REG 15513 Example mapping reading from slave ID 2 Modbus register 10001 discrete input 1 which is sent to AP register 15513 Selecting this menu i...

Страница 25: ...sensor diagnostic d Send manual command Send manual command to add sensor Use this option if more than one sensor connected to bus e SDI Sampling Time Configure the SDI sensor system sample time in mi...

Страница 26: ...then configure the sensitivity zero offset display units as required for the application Note that all SDI 12 measurement variables are sent as floating point values Select the letter corresponding t...

Страница 27: ...ail Time can be configured from the Unit menu If there is a communications failure the Outputs Timeout value can be configured from the Unit menu to reset outputs to default state to allow plant or eq...

Страница 28: ...atch for pulsed output b Sensor REG Register used for input or output c Latching pulse duration For Latched or pulsed outputs configuration of time that output is ON or active d Save Config e Return t...

Страница 29: ...eeded to de encrypt the file The file name used when saved includes the units serial number and Station name which allows multiple files to be saved onto USB and then recovered very quickly to load in...

Страница 30: ...o be done manually Successfully saved config file to USB Drive Press any key to continue Write to USB memory device has been completed When menu option to read configuration file Save to filename 0123...

Страница 31: ...s it all off c SDI 12 value Test Test functions for SDI 12 sensor to allow reading changing of sensor address info commands etc to allow fault diagnosis d Modbus Testing Test the Modbus functionality...

Страница 32: ...onfigured before this menu can be accessed Will scan the Modbus and then display the I O menu below a Read Coil b Read Discrete c Read Registers d Read Inputs e Write Coils f Write Registers g Write C...

Страница 33: ...Enable disable Console option Function stays enabled disabled until menu is reselected Enable monitoring radio communication Enable disable Monitor Radio Comms logging This feature gives you a detail...

Страница 34: ...o 802 11 protocol Some common values are shown here 8000 Beacon frame from AP D400 ACK message acknowledge 0000 Association Request 1000 Association Response 4000 Probe Request 5000 Probe Response 080...

Страница 35: ...chnician time to take action if required Restore factory default configuration Factory defaults can be reset either through Unit Config Restore Default configuration menu option or through button push...

Страница 36: ...es Topology Remote Unit type Input and Output Discrete Inputs Outputs Input 4 x digital I O configurable as on off or DI1 3 pulse inputs On state voltage 2 Vdc Off state voltage 3 Vdc Wetting current...

Страница 37: ...utton Sequence Reported Diagnostics Radio Diagnostics Monitoring communications RSSI measurements Antenna fail Background noise low battery voltage Modbus communications fail External internal inputs...

Страница 38: ...FePO Internal LiP non rechargeable Lithium Thionyl Chloride LiSOCI2 External 12Vdc Lead acid or Lithium Iron Phosphate LiFePO charge current max 2A Solar Regulator or Battery Charger External power su...

Страница 39: ...Input registers words 30001 30004 Local AI1 AI4 analog inputs current mode AI1 and AI2 4 20 mA differential AI3 and AI4 4 20 mA sink 30005 Local supply voltage 0 40 V scales to 0 20mA 30006 Local 24...

Страница 40: ...mary connection data rate Upstream data rate 30426 30490 Spare General purpose word storage used for Staging area for data concentrator Fieldbus mappings storage 30491 Logic Engine Execution State 0 S...

Страница 41: ...ched 115s expansion I O modules Twenty registers per module address maximum number of modules is 19 40401 46000 General purpose word storage area used for Staging area for data concentrator Fieldbus m...

Отзывы: