User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
28
f) Analog 2
g) Battery Voltage
h) Solar/Supply Voltage
i) RSSI
j) Internal Temp
j) Internal Temp
k) Status Sensor
l) Analog Set Points
m) SDI-12 Device config
n) Analog Sampling
o) Return to Main menu
When configuring simple ON/OFF discrete outputs, then simple select the digital output menu option
to configure settings.
For Pulsed (latched) outputs the discrete outputs are paired. To configure select discrete 1 or discrete
3. For example if discrete output 1 is configured as pulsed, when this output is set ON the physical
DIO1 will pulse ON for the configured duration. When set to OFF, then DIO2 will pulse ON for the
configured duration. This configuration allows the use of low power latching solenoids or relays to be
used.
To configure a digital as an output, select DIO mode see menu options below:
DO1
Mode
Latch1
REG
37011
LPD
Value
Digital 1 Menu:
a) DIO mode
Select Discrete as Input or Output. If Output is
selected, then can be configured as ON/OFF or Latch
for pulsed output.
b) Sensor REG
Register used for input or output
c) Latching pulse duration
For Latched or pulsed outputs configuration of time
that output is ON or active.
d) Save Config
e) Return to previous menu
For discrete and pulsed (latched) outputs there are two other configuration items available. Output
Tail Time is configured with a time in seconds which will keep the 415U-1-Cx powered and able to
receive messages from the access point. This configuration can be used in applications where a 415U-
1-Cx sensor input might be known to possible trigger the activation of a discrete output. So, it will
allow this output to be received while and minimize latency.
If the application is not time critical then it is best to keep the Output Tail Time to a minimum value or
zero to maximize battery life.
Output Timeout can be used to reset outputs to a failsafe state if the 415U-1-Cx has lost
communication with the access point. This setting is a timeout value and should be set to a value
longer than the update time. A recommendation is to use 2.5 times the update time.
Configuration of the Output Tail Time and the Output Timeout can be found in the Unit config menu,
accessed from the Main menu.
Unit Config Menu: