discrete input alarm or control signal to be created that for example could be used to control a high or
low level alarm.
The high and low set point values that used for the internal set point discrete input are either from
configurable default values or from a register that can be written to remotely. The default is used
when the unit is reset and until a value is written into the high or low register if configured.
Analog set point menu can be accessed from the I/O Setup menu and will display as below.
SP1
ASP1OFF
ASP1ON
REG
15501
35501
35502
Actual
On
90
10
Value
On
90%
10%
Analog Set Point Menu:
a) AN1 Set Point
Configure analog input 1 setpoint registers, high/low
default and register values.
b) AN2 Set Point
Configure analog input 1 setpoint registers, high/low
default and register values.
c) Return to Main menu
For each analog set points there is the flowing configurable parameters:
•
Internal setpoint discrete register.
•
Setpoint High Level default value at which the internal input is set to OFF if analog value is
greater than.
•
Setpoint High Level register that if set with a value will override the configured default value.
•
Setpoint Low Level default value at which the internal input is set to ON if analog value is less
than.
•
Setpoint Low Level register that if set with a value will override the configured default value.
Selecting the configuration for AN1 Set Point will display the following menu:
Analog Set Points: