Chapter Three
Installation
MAN_905G_1.16
Page 36
3.6
Profibus Port
The Profibus RS485 connector is a D9 connector in the top end-plate of the module (see
below).
905U-G-PR1 (Profibus Slave) End Plate:
Note: If the “Use Rotary Switch Address” option in configuration software is selected, the
two rotary switches are used to specify the Profibus Node Address in the range 0 – 99. In this
case, the value on the left switch is multiplied by 10 and added to the value on the right
switch to give the node address.
Where the 905G module is mounted at the end of the RS485 link, the RS485 link should be
terminated by switching the termination switch “on” (down in the above diagram).
905U-G-PR2 (Profibus Master) End Plate:
For the Profibus Master 905G a second, unused, connector is also present.
The Profibus RS485 connection should be made to pins 3 and 8 of the Profibus D9 connector.
The pinouts for this connector are:
ANTENNA
CONNECTION
PROFIBUS D9
CONNECTOR
SELECTOR
SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
RS485
TERMINATION
SWITCH
ANTENNA