Technical Support Line +44 (0)2392 696638                                   G240xBM-x-y  PAK200536_01G May 2016                    Elmdene International Ltd © 

Standby Battery 

Battery Type 

2 x 12V Valve Regulated Lead Acid 

Battery Capacity 

See below under enclosure size. 

Battery Charging Fuse protection 

See Model Specification Table 

Battery Re-Charge Time 

<24hrs (to 80% of 8Ah capacity) 

 

Mechanical  

Model 

Enclosure 

Dimensions  

w x h x d [external] (mm) 

Max Battery 

Capacity 

Weight (kg) 

[excluding battery]

 

G240xBM-C

 

330 x 275 x 80 

2 x NP7 (7Ah) 

G2401BM

 

3.16 

G2402BM 

3.22 

G2403BM, G2405BM

 

3.30 

G240xBM-R

 

390 x 410 x 80 

2 x NP17 (17Ah) 

G2401BM

 

6.03 

G2402BM

 

6.09 

G2403BM, G2405BM

 

6.17 

G240xBM-H

 

420 x 420 x 180 

2 x NP38 (38Ah) 

G2403BM, G2405BM

 

8.53 

 

Environmental  

Temperature  

-10 to +40°C (operating) 75% RH non-condensing  

 

-20 to +80°C (storage) 

 

 

S

IGNALLING 

O

UTPUTS

 

 

 

GEN Fault (general) 

0.1 A @ 60 VDC N/O volt-free contact. 
Open when battery disconnected, output fuse fail, battery fuse fail, 
output short circuit or low output voltage. 

EPS Fault (mains) 

0.1 A @ 60 VDC N/O volt-free contact. 
Open when loss of mains for more than 8s. 

 

C

ONNECTIONS

   

 

O/P +, - 

Connection to equipment to be powered (Observe polarity) 

 

BATT +, - 

Connection to standby battery. Use cables provided (Observe polarity) 

GEN Fault  

Volt-free contacts for general faults 

EPS Fault 

Volt-free contacts for loss of mains indication 

 

I

NSTALLATION 

I

NSTRUCTIONS

 

 

 

This unit is only suitable for installation as permanently connected equipment.  This PSU is

 

NOT SUITABLE 

for external 

installation. This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted 
with a fuse or other over-current protection device rated at 3A maximum. Ensure that the disconnect device used has 
appropriate  earth  fault  protection  to  the  applicable  standard. 

EQUIPMENT  MUST  BE  EARTHED

.  Before  installation, 

ensure that external disconnect device is

 OFF

.

 

The PSU should be installed according to all relevant safety regulations 

applicable to the application.  

 

Mounting 

1)

 

Mount securely in correct orientation allowing minimum clearance – see diagram. 

2)

 

Route mains and low voltage output cables via different knockouts and/or cable entry holes. 

3)

 

Use bushes and cable glands rated to UL94 HB minimum.  

 

Mains Power Up 

4)

 

Attach correctly rated mains cable (minimum 0.5mm

2

 [3A], 300/500Vac). Fasten with cable ties. 

5)

 

Apply mains power. Check for 27.6Vdc on load outputs. Check Green Mains LED is ON. 

6)

 

Disconnect mains power.  