background image

4

 

Technical Support Line +44 (0)2392 696638                                   G240xBM-x-y  PAK200536_01G May 2016                    Elmdene International Ltd © 

M

AINTENANCE

   

 

There  is  no  regular  maintenance  required  of  the  PSU  other  than  periodic  testing  and  replacement  of    the  standby 
batteries.   

Reference  should  be  made  to  the  battery  manufacturer’s  documentation  to determine typical/expected 

battery life with a view to periodic replacement of the battery.   

 
If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load.  The fault should be 
rectified before restoring power to the PSU.  The fuses may need to be replaced.  Ensure the correct fuse rating and 
type is used. 

 

L

OCAL 

I

NDICATORS

 

 

 

M

AINS 

LED

 

(

GREEN

F

AULT 

LED

 

(

YELLOW

C

HARGE 

LED

 

(

ORANGE

S

TATUS

 

ON 

OFF 

OFF 

NORMAL - battery fully charged 

ON 

OFF 

ON 

NORMAL - battery charging 

ON 

1s ON, 1s OFF 

ON or OFF 

FAULT - see Signalling Outputs 

OFF 

0.1s ON, 3s OFF 

OFF 

FAULT - Mains Loss 

PSU operating on battery 
standby 

OFF 

OFF 

OFF 

FAULT - No Output 

Mains and Battery loss 

 

C

OMPLIANCE

   

 

This power supply unit meets the essential requirements of the following European Directives: 
Low Voltage: 2014/35/EU 

 

EMC: 2014/30/EU 

WEEE: 2012/19/EU 

 

RoHS2: 2011/65/EU 

 

D

ISPOSAL OF 

P

RODUCT AT 

E

ND OF 

L

IFE

 

 

 

This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and 
2013/56/EU (Battery). At the end of life, the product must be separated from the domestic waste stream and disposed 
via an appropriate approved WEEE disposal route in accordance with all national and local regulations. 
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate approved 
battery disposal route in accordance with all national and local regulations. Package used batteries safely for onward 
transport to your supplier, collection point or disposal facility. 

Caution:  Risk of fire or explosion if bare battery wires are allowed to touch. 

See Specification for battery type information. The battery is marked with the crossed out wheelie bin symbol, which 
may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). 

For more information see: 

www.recyclethis.info

 

 
 
 
 
 
 
 
 

 

The packaging supplied with this product may be recycled. 

 Please dispose of packaging accordingly.

 

 

       

 

Отзывы: