background image

3

 

Technical Support Line +44 (0)2392 696638                                   G240xBM-x-y  PAK200536_01G May 2016                    Elmdene International Ltd © 

Load Output

 

7)

 

Attach correctly rated load cable and fasten using cable ties. Note polarity. 

8)

 

Apply mains power. Check Green Mains LED is ON.  

9)

 

NOTE: Yellow Fault LED may flash to indicate no battery has been connected. This is normal. 

10)

 

Verify load is operating correctly. 

11)

 

Disconnect mains power. 

 

          

 

 

G2401BM, G2402BM 

G2403BM, G2405BM              

Signalling Outputs 

12)

 

Connect EPS and GEN fault outputs to appropriate inputs of control equipment. 

 

Standby Battery 

13)

 

Attach supplied battery cables to terminal block and batteries. NOTE: ensure correct polarity!  
Red lead to +ve of battery 1, Black lead to   -ve of battery 2. 

            Connect -ve of battery 1 to +ve of battery 2 using short link lead  
14)

 

Apply mains power. Check Green Mains LED is ON and Orange Charging LED is ON 

15)

 

Check there is no fault indication on Yellow Fault LED. 

16)

 

Disconnect mains power. Check that the batteries continue to supply voltage and current to the load. Check 
Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault.

 

NOTE

: Batteries must have sufficient charge to supply the load 

17)

 

Reconnect mains power. Check Green Mains LED is ON. 

18)

 

Remove Load fuse and check Yellow Fault LED is ON and control panel shows a General PSU fault. 

19)

 

Replace Load fuse. Check Yellow Fault LED is OFF and General PSU fault has cleared at the control panel 

 

M

ODEL 

S

PECIFICATION 

T

ABLE

 

 

 

 

G2401BM 

G2402BM 

G2403BM 

G2405BM 

Output Current 

1A 

2A 

3A 

5A 

Max Mains Input Current 

(at 90Vac) 

1.0A 

1.3A 

1.4A 

2.0A 

Mains Input Fuse (20mm HRC) 

T2.0A 

T2.0A 

T3.15A 

T3.15A 

Output Fuse (20mm) 

F1.0A 

F2.0A 

F3.15A 

F5.0A 

Battery Fuse (20mm) 

F1.0A 

F2.0A 

F3.15A 

F5.0A 

 

O

PERATING 

I

NSTRUCTIONS

 

 

 

This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts inside. 

 

The Green Mains LED will be illuminated whilst the mains supply is present. In the event of a fault condition, the Yellow  
Fault LED will be illuminated. 

 

The  Orange  Battery  Charging  LED  will  be  illuminated  when  the  battery  is  not  fully  charged  and  is  charging  normally. 
When the battery is fully charged, this LED will be extinguished. 

 
 

10cm all round  

.


10cm all round  

.

L E N 

Отзывы: