27.6 Vdc Switch Mode Power Supply for Fire – EN54-4:1997 +A1 +A2 

STX2410-E     Optional BATT-BOX-65 
STX2410-H 

 
 

F

EATURES

 

 

 
The STX2410-x is an EN54-4:1997 +A1 +A2 approved power supply ideal for use in Fire control 
Systems. Its regulated 27.6V dc output will supply a total of 10 Amps continuous into the load, whilst 
also enabling battery charging. (7.2 Amps Load with 65Ah batteries, 10 Amps with 18Ah batteries).The 
power supply output features electronic short circuit protection under both mains and standby 
battery operation. Maximum battery life is assured through continuous active battery monitoring and 
the use of a three stage charger, comprising bulk, absorb and temperature compensated final float 
phase depending upon battery condition. Once fully charged the product operates in Eco power 
saving mode, whereby the batteries are charged for 4 hours in every 24 hour period while still being 
continuously monitored. This reduces wasted energy in charging already fully charged batteries and 
extends their working life.  Deep discharge protection prevents premature battery failure when 
operating from standby for extended periods. Two sets of volt free solid state relay fault output signal 
(i) loss of mains and (ii) battery fault, charger fault and loss of output. In addition there is an RS232 
serial interface that can provide diagnostic and fault reporting information to supervisory systems.  
 

 

Certified by UL to EN54-4:1997 +A1 +A2.  

 

Up to 10 A current to load at 27.6V dc nominal regulated output. 

 

Charging capability to support 18, 38 or 65Ah batteries with intelligent load enhancement. 

 

Electronic overload protection shuts down output until overload or short circuit is removed. 

 

Battery Monitor detects battery missing, low battery, short-circuit or reverse connection or 
circuit impedance (Ri) in excess of 300m

 caused by connector or wiring  corrosion within 

4hours.. 

 

Battery charging circuit is energised only when a battery is correctly connected and the battery 
voltage is greater than 14 V. 

 

No loss of output during automatic connection of battery to load on loss of mains. 

 

Deep discharge protection disconnects battery from load when battery voltage falls to 21 V. 

 

Fault indicator LED (Yellow) flashes on detection of output fault, battery fault, charger fault and 
mains failure. 

 

Mains indicator LED (Green) showing mains present. 

 

RS232 serial interface for fault reporting and diagnostics interface to OEM equipment. 

 

                

 

 
Elmdene International Ltd

 

 

Tel:  +44(0)23 9269 6638 

3 Keel Close, Interchange Park, 

 

Fax:  +44(0)23 9266 0483 

Portsmouth, Hampshire, PO3 5QD, UK 

Web:   

www.elmdene.co.uk

 

 

0843-CPR-0216 

14 

Содержание BATT-BOX-65

Страница 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Страница 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Страница 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Страница 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Страница 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Страница 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Страница 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Страница 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Страница 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Страница 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Отзывы: