Batt 

LED #2 

Condition 

Possible Cause 

Action 

 

GREEN/YELLOW  

Fast

 Flash 

Battery 
in process of connecting 

Battery connecting 

 

No action –  
Wait for battery connection to complete

 

 

GREEN Flash

 x1

 

Normal operation 
(Battery connected) 

Battery in bulk charge  

No action –  
Battery charging normally

 

 

GREEN

 

Normal operation 
(Battery connected) 

Battery healthy.

 

No action –  
System healthy. 

(Battery in good state of charge)

 

 
 

 

YELLOW

 

Battery fault

 

Battery disconnected 
Low Battery Volts 
High impedance in battery 
connection. 
Battery internal fault (detected 
during load test). 

Note LED #4 Flash sequence and refer to 
table 

 

Fault 

LED #3

 

Condition 

Possible Cause 

Action 

 

OFF

 

Normal Conditions 

No faults 

No action  

 

 

YELLOW  
Flash

 x1

 

PSU Fault 
 

See LED #4 Flash sequence table

  

Note LED #4 Flash sequence and refer to 
table 

 

Diagnostic 

LED #4 

Condition 

Possible Cause 

Action 

 

RED  

Flash

 x1 

No Output 

Output fuse fail 
Output overload or 
short circuit. 

Check and replace output fuse. 
Disconnect and test output load. 

 

 

RED 

Flash

 x2

 

No Battery  
Low Battery Volts.

 

Battery disconnected  
Battery heavily discharged 
Low Battery Volts 

Check battery connections 
Check battery fuse. 
Check battery condition / replace battery. 

 

RED  

Flash 

x3

 

Battery Fault. 

High impedance in battery 
connection. 
Battery internal fault (detected 
during load test). 

Check battery connections for corrosion. 
Replace battery if aged. 

 

RED  

Flash

 x4

 

Charger Fault. 

Internal failure of battery charger. 

Return to manufacturer. 

 

 

RED  

Flash 

x5

 

Battery Temperature Probe 
Fault. 

Battery temperature monitor 
disconnected or damaged. 
PSU running in Safe Mode. 

Check temperature sensor connections 
and condition of sensor. 
Replace if suspect 

 

RED  

Flash 

x6

 

Dual Path Fault. 

Fault in output connections to the 
load 
(DUAL-PATH mode active only). 

Check all cables between PSU and load. 

 
 
 

 
 

 

Содержание 2405ST Series

Страница 1: ... Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final commissioning 8 Operating Instructions and Maintenance 9 Trouble shooting 10 Developer Section DUAL PATH RS485 communication link 11 Disposal and Product Compliance Elmdene International Ltd Tel 44 0 23 9269 6638 3 Keel Close Interchange Park Fax...

Страница 2: ...r an output voltage 50 Un Fuse Load OP1 and OP2 F5 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours with monitored ECO charging Battery Voltage Low battery threshold voltage Deep discharge protection 23 2 V measured at the battery 21 6 V minimum measured at PSU output Quiescent current At no load At battery cu...

Страница 3: ...s used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 5 The low voltage output cable must be sized to carry the rated load current to...

Страница 4: ...onnect the mains power using the disconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED COM TO N C CLOSED Normal operation Mains present Battery healthy None COM TO N C OPEN COM TO N C CLOSED Standby Mode Mains lost 8 seconds Battery driving load Investiga...

Страница 5: ...r Setting 21 Set the correct charger mode by fitting the jumper to the appropriate charger mode header Use the table below to select the appropriate charger mode Battery mode selected Mode 1 DEFAULT Mode 2 Mode 3 Battery Capacity 2x 12V 7 Ah 12 Ah 17 Ah 24 Ah 38 Ah 65Ah EN54 4 Continuous Output Current No charging Imax B With Charging Imax A 5 7 A c 5 0 A 5 7 A b 4 0 A 5 7 A 3 0 A Constant current...

Страница 6: ...24 Ensure all battery terminals are sufficiently insulated to prevent accidental shorting to each other or the enclosure metalwork Warning Always use two 12V batteries connected in series This product will not work with one 12V battery 25 The Battery box is used for 65 Ah batteries and designed to be floor mounted DO NOT suspend from wall 26 It is important that the battery box and the PSU are co ...

Страница 7: ...he free positive battery terminal and the black battery lead to the free negative battery terminal CAUTION significant energy can be released from an SLA battery When connecting the last battery lead take extreme care to attach the cable ONLY to the correct terminal Avoid shorting it to any other terminal or conducting surface CAUTION the supplied battery lead contains a temperature sensor DO NOT ...

Страница 8: ... Indication Output 2 OK See also Status and Fault Diagnostic LED Indication table for full details of LED indications 38 If connected verify that EPS Fault output shows a com to n c closed contact and the GEN PSU Fault output also shows a com to n c closed contact 39 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact exposed metal w...

Страница 9: ... the PSE other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery TROUBLE SHOOTING Front Panel Legend The PSU will identify a fault the PSU LED3 Further information can be obtained by observing the flash sequence of LED 4 and u...

Страница 10: ...able Note LED 4 Flash sequence and refer to table Diagnostic LED 4 Condition Possible Cause Action RED Flash x1 No Output Output fuse fail Output overload or short circuit Check and replace output fuse Disconnect and test output load RED Flash x2 No Battery Low Battery Volts Battery disconnected Battery heavily discharged Low Battery Volts Check battery connections Check battery fuse Check battery...

Страница 11: ...e header marked OP1 OP2 This mode meets the requirements of EN54 13 Section 5 3 3 1 SFAULT and Section 5 3 4 2 PFAULT warning conditions for loads above 200mA It is still necessary for the connected equipment to be designed to accept two separate power inputs such that a short to ground of either power transmission path will not inhibit the equipment performance PSU Addressable Data link communica...

Страница 12: ...ery type information The battery is marked with the crossed out wheelie bin symbol which may include lettering to indicate cadmium Cd lead Pb or mercury Hg For more information see www recyclethis info The packaging supplied with this product may be recycled Please dispose of packaging accordingly COMPLIANCE This power supply unit meets the essential requirements of the following EU Directives CPR...

Отзывы: