9
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD
O
PERATING
I
NSTRUCTIONS
In the event of loss of mains, a battery fault or a GEN fault, the corresponding Fault relay (signal) contacts
will open, and the LED indicators will display the fault condition and overall status of PSE.
If the output of the PSE fails, the cause of the failure should be investigated, also by referring to the ’
Status
and Fault-Diagnostic LED Indication‘
table, e.g. short circuit on load terminals or connection of a deeply
discharged battery. The fault should be rectified before restoring power to the PSE.
If any of the fuses require replacing, ensure the correct fuse rating and type is used – see page 2
M
AINTENANCE
This unit is intended for use by Service Personnel only. There are NO USER SERVICEABLE parts inside.
There is no regular maintenance required of the PSE other than periodic testing, and replacement of the
standby battery.
Reference should be made to the battery manufacturer's documentation to determine
typical/expected battery life with a view to periodic replacement of the battery.
T
ROUBLE
S
HOOTING
Front Panel Legend
The PSU will identify a fault the PSU (LED3)
Further information can be obtained by observing the flash sequence of LED 4 and using the tables below
LED KEY
ON
OFF
FLASHING ON/OFF
FLASHING GREEN/YELLOW
Mains
LED #1
Condition
Possible Cause
Action
GREEN
Mains OK
YELLOW
Mains lost
(Battery supporting load)
Mains lost /
Battery supporting load.
Investigate loss of mains.
OFF
PSU off
– No power
(Battery depleted)
Mains lost /
Battery not supporting load.
Restore mains, confirm batteries are in
working condition
#
Indicator
Functional states
1
Mains status
Fault / Standby (support) operation / OK
2
Battery status
Battery Fault / Bulk Charging / Battery OK
(charged)
3
Fault status
No Fault(s) / GEN (PSU) Fault
4
Diagnostic
status
See ‘
Status and Fault-Diagnostic LED
(Indication’
table, below)
5
OP1 status
Fault / OK
6
OP2 status
Fault / OK