background image

11 

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200789_02A July 2019                        ©2019 ELMDENE INTERNATIONAL LTD  

OP1 & OP2 

LEDs #5 or #6

 

Condition 

Possible Cause 

Action 

 

GREEN

 

Normal operation 

No faults. 

No action 

 

 

 

YELLOW

 

No Output 

Output fuse fail 
Output overload or 
short circuit. 

Check and replace output fuse. 
Disconnect and test output load. 

 

 

NOTE: after applying mains power – if red LED is ON (not flashing), this indicates a failed calibration check, although a calibration fault 
is not indicated via the GEN fault relay. This fault should never be seen, but in the extremely rare event that it does, the PSU will 
operate using default values, but some functions may be compromised, and you are strongly advised to contact Elmdene Technical 
Support to return the product. Indication of a calibration fault will be suppressed (but not cleared) when the battery is connected. 
 

D

EVELOPER 

S

ECTION 

 

 

Figure 4 – Terminal layout and mode selection 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
Dual-Path power transmission monitoring feature 

43.

 

The 2405ST PSU has an optional mode designed to 

work with systems that require dual-power 

transmission paths.  When enabled, the PSU compares 
the outputs and reports a load imbalance of more than 

10% as an OUTPUT FAULT (LED 4 x6 Flashes) and is 

enabled by removing the header marked 

OP1 

 OP2

 

 

This mode meets the requirements of EN54-13 Section 

5.3.3.1 S

FAULT 

and Section 5.3.4.2 P

FAULT 

warning 

conditions, for loads above 200mA. 

It is still necessary for the connected equipment to be 

designed to accept two separate power inputs, such 

that a short to ground of either power transmission 
path, will not inhibit the equipment performance. 

 

 

PSU Addressable Data link communication protocol 

 

44.

 

The 2405ST PSU has an addressable RS485 communication port, that can be enabled to provide the 

internal PSU data, and includes; Mains Voltage; Output1 Voltage/Current; Output2 Voltage/Current; 
Battery Voltage; Charger Current; Charger setting; GEN Fault condition; EPS Fault condition; Diagnostics 

fault status (condition 1-6), Battery temperature, Charger status, unit address 

45.

 

To enable this feature and obtain the protocol guide, please contact Elmdene Technical Support  

Mains 

Input 

Load 

Outputs 

Battery 

Connection 

 

GEN & EPS 

Relay Outputs 

 

‘No battery’ 

Select 

 

Unit Add 

Select 

RS485 

Link 

Temp Probe 

Inputs 

OP2 

Fuse 

PTC Battery 

Fuse 

OP1 ≠ OP2 

Select 

LED Status 

Indicators 

Charger 

Setting 

OP1 

Fuse 

Mains  

Fuse 

OP1≠OP2 

DUAL-PATH ACTIVE 

DUAL-PATH MODE FAULT SIGNALLING

-

PSU LOAD OUTPUT

1    &    2

+

DU AL PATH LOAD I NPUT

-

+

-

+

FA ULT SIGNALLED WHEN 

M O RE T HAN 1 0% 
I M BALANCE BETWEEN 

P A THS 

RE F: E N 54-13 5 .3 .4.1 S

FAULT 

& 5 .3 .4 .2  P

FAULT 

V ALUES

+

-

* E quipment must be have 2 s eparate power inputs c apable of 

withs tanding a s hort to ground on one path

 

Содержание 2405ST Series

Страница 1: ... Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final commissioning 8 Operating Instructions and Maintenance 9 Trouble shooting 10 Developer Section DUAL PATH RS485 communication link 11 Disposal and Product Compliance Elmdene International Ltd Tel 44 0 23 9269 6638 3 Keel Close Interchange Park Fax...

Страница 2: ...r an output voltage 50 Un Fuse Load OP1 and OP2 F5 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours with monitored ECO charging Battery Voltage Low battery threshold voltage Deep discharge protection 23 2 V measured at the battery 21 6 V minimum measured at PSU output Quiescent current At no load At battery cu...

Страница 3: ...s used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 5 The low voltage output cable must be sized to carry the rated load current to...

Страница 4: ...onnect the mains power using the disconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED COM TO N C CLOSED Normal operation Mains present Battery healthy None COM TO N C OPEN COM TO N C CLOSED Standby Mode Mains lost 8 seconds Battery driving load Investiga...

Страница 5: ...r Setting 21 Set the correct charger mode by fitting the jumper to the appropriate charger mode header Use the table below to select the appropriate charger mode Battery mode selected Mode 1 DEFAULT Mode 2 Mode 3 Battery Capacity 2x 12V 7 Ah 12 Ah 17 Ah 24 Ah 38 Ah 65Ah EN54 4 Continuous Output Current No charging Imax B With Charging Imax A 5 7 A c 5 0 A 5 7 A b 4 0 A 5 7 A 3 0 A Constant current...

Страница 6: ...24 Ensure all battery terminals are sufficiently insulated to prevent accidental shorting to each other or the enclosure metalwork Warning Always use two 12V batteries connected in series This product will not work with one 12V battery 25 The Battery box is used for 65 Ah batteries and designed to be floor mounted DO NOT suspend from wall 26 It is important that the battery box and the PSU are co ...

Страница 7: ...he free positive battery terminal and the black battery lead to the free negative battery terminal CAUTION significant energy can be released from an SLA battery When connecting the last battery lead take extreme care to attach the cable ONLY to the correct terminal Avoid shorting it to any other terminal or conducting surface CAUTION the supplied battery lead contains a temperature sensor DO NOT ...

Страница 8: ... Indication Output 2 OK See also Status and Fault Diagnostic LED Indication table for full details of LED indications 38 If connected verify that EPS Fault output shows a com to n c closed contact and the GEN PSU Fault output also shows a com to n c closed contact 39 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact exposed metal w...

Страница 9: ... the PSE other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery TROUBLE SHOOTING Front Panel Legend The PSU will identify a fault the PSU LED3 Further information can be obtained by observing the flash sequence of LED 4 and u...

Страница 10: ...able Note LED 4 Flash sequence and refer to table Diagnostic LED 4 Condition Possible Cause Action RED Flash x1 No Output Output fuse fail Output overload or short circuit Check and replace output fuse Disconnect and test output load RED Flash x2 No Battery Low Battery Volts Battery disconnected Battery heavily discharged Low Battery Volts Check battery connections Check battery fuse Check battery...

Страница 11: ...e header marked OP1 OP2 This mode meets the requirements of EN54 13 Section 5 3 3 1 SFAULT and Section 5 3 4 2 PFAULT warning conditions for loads above 200mA It is still necessary for the connected equipment to be designed to accept two separate power inputs such that a short to ground of either power transmission path will not inhibit the equipment performance PSU Addressable Data link communica...

Страница 12: ...ery type information The battery is marked with the crossed out wheelie bin symbol which may include lettering to indicate cadmium Cd lead Pb or mercury Hg For more information see www recyclethis info The packaging supplied with this product may be recycled Please dispose of packaging accordingly COMPLIANCE This power supply unit meets the essential requirements of the following EU Directives CPR...

Отзывы: