(follow steps 29-30). Once the batteries are charging, clear the thermistor fault by reconnecting the 

thermistor wire. 

 

32.

 

Verify GEN Fault relay n/c contact is 

closed

, (com to n/c terminals = short circuit) 

33.

 

Disconnect the mains power. Verify that the green Mains LED #1 extinguishes, and the Yellow Fault LED 

#3 starts to flash (indicating that the PSE is running from its standby batteries). 

34.

 

If connected, verify that the EPS Fault output shows an 

open

 contact (com and n/c terminals = open 

circuit) and the GEN PSU Fault output shows a 

closed

 contact (com and n/c terminals = short circuit). 

35.

 

Verify that the standby batteries are now supporting the system load. Perform a full functional test of 

system including full alarm condition Note: ensure batteries have sufficient charge to support the 
system under full load.

 

36.

 

To prevent battery fault indication when no battery 

is required, fit the “No Battery” link (            ).  

 

Please note; fitting of this link invalidates EN54-4, 

EN12101-10 and NF S 61-940 compliance. 

 

Final Commission 

37.

 

Reconnect the mains. Verify that 

 

LED # 

Symbol 

LED Colour

 

Function

 

Mains 

Constant Green 

Indication: Mains supply = OK 

Batt 

Green flash x1 

(repeating) 

Indication: Battery Charging (bulk phase)

 

Fault 

OFF 

Indication: No Fault 

Diagnostic 

OFF 

Indication: No Fault 

OP1 

Constant Green 

Indication: Output 1 = OK 

OP2 

Constant Green 

Indication: Output 2 = OK 

 

(See also ‘

Status and Fault-Diagnostic LED Indication

‘ table for full details of LED indications.) 

 

38.

 

If connected, verify that EPS Fault output shows a (com to n/c) 

closed

 contact and the GEN PSU Fault 

output also shows a (com to n/c) 

closed

 contact. 

39.

 

Disconnect one of the battery leads, ensuring that no exposed section of conductor or connector is 

allowed to contact exposed metal-work, other PSE terminals, or other battery terminals. 

 

40.

 

Verify that, in less than 1 minute the following conditions are met: 

 

LED # 

Symbol 

Green ON 

Function

 

Batt 

Constant Yellow 

Indication: Battery Fault = missing battery indicated

 

Fault 

Yellow flash x1 (repeating 

Indication: Fault with PSU = due to missing battery 

Diagnostic 

Red flash x2 (repeating) 

Indication: Fault = missing battery indicated 

OP1 

Constant Green 

Indication: Output 1 = OK 

OP2 

Constant Green 

Indication: Output 2 = OK 

Batt 

Constant Yellow 

Indication: Battery Fault = missing battery indicated

 

 
(See also ‘

Status and Fault-Diagnostic LED Indication

 table for full details of LED indications.) 

 

41.

 

Reconnect the battery lead and, after approximately 3s, verify that that the Fault LED #3 does not flash. 

(Audible click can be heard as the battery relay closes, then a second click while the charger is tested.)  

Note: If it is necessary to obtain confirmation of charging current; between steps 28 and 29, an ammeter 

can be placed in series with the battery leads. Continue to observe caution with all exposed conductors 

when inserting or removing the meter and when restoring normal battery wiring 

 

42.

 

Close cover and secure using fastening screws provided. 

 

 

- + -

T T

FAULT OUTPUTS

FUSE  #1

FUSE  #2

 

Содержание 2405ST Series

Страница 1: ... Installation cont Battery Charger settings 6 Installation cont Battery installation Battery compatibility 7 Installation cont Battery installation Final commissioning 8 Operating Instructions and Maintenance 9 Trouble shooting 10 Developer Section DUAL PATH RS485 communication link 11 Disposal and Product Compliance Elmdene International Ltd Tel 44 0 23 9269 6638 3 Keel Close Interchange Park Fax...

Страница 2: ...r an output voltage 50 Un Fuse Load OP1 and OP2 F5 0 A IEC 60127 2 type Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours with monitored ECO charging Battery Voltage Low battery threshold voltage Deep discharge protection 23 2 V measured at the battery 21 6 V minimum measured at PSU output Quiescent current At no load At battery cu...

Страница 3: ...s used for other applications it should be installed according to all relevant safety regulations applicable to that application Cable Sizing 4 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 5 The low voltage output cable must be sized to carry the rated load current to...

Страница 4: ...onnect the mains power using the disconnect device Connecting the Remote Signalling 14 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of CIE EPS Fault GEN Fault Condition Possible Cause Action COM TO N C CLOSED COM TO N C CLOSED Normal operation Mains present Battery healthy None COM TO N C OPEN COM TO N C CLOSED Standby Mode Mains lost 8 seconds Battery driving load Investiga...

Страница 5: ...r Setting 21 Set the correct charger mode by fitting the jumper to the appropriate charger mode header Use the table below to select the appropriate charger mode Battery mode selected Mode 1 DEFAULT Mode 2 Mode 3 Battery Capacity 2x 12V 7 Ah 12 Ah 17 Ah 24 Ah 38 Ah 65Ah EN54 4 Continuous Output Current No charging Imax B With Charging Imax A 5 7 A c 5 0 A 5 7 A b 4 0 A 5 7 A 3 0 A Constant current...

Страница 6: ...24 Ensure all battery terminals are sufficiently insulated to prevent accidental shorting to each other or the enclosure metalwork Warning Always use two 12V batteries connected in series This product will not work with one 12V battery 25 The Battery box is used for 65 Ah batteries and designed to be floor mounted DO NOT suspend from wall 26 It is important that the battery box and the PSU are co ...

Страница 7: ...he free positive battery terminal and the black battery lead to the free negative battery terminal CAUTION significant energy can be released from an SLA battery When connecting the last battery lead take extreme care to attach the cable ONLY to the correct terminal Avoid shorting it to any other terminal or conducting surface CAUTION the supplied battery lead contains a temperature sensor DO NOT ...

Страница 8: ... Indication Output 2 OK See also Status and Fault Diagnostic LED Indication table for full details of LED indications 38 If connected verify that EPS Fault output shows a com to n c closed contact and the GEN PSU Fault output also shows a com to n c closed contact 39 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact exposed metal w...

Страница 9: ... the PSE other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery TROUBLE SHOOTING Front Panel Legend The PSU will identify a fault the PSU LED3 Further information can be obtained by observing the flash sequence of LED 4 and u...

Страница 10: ...able Note LED 4 Flash sequence and refer to table Diagnostic LED 4 Condition Possible Cause Action RED Flash x1 No Output Output fuse fail Output overload or short circuit Check and replace output fuse Disconnect and test output load RED Flash x2 No Battery Low Battery Volts Battery disconnected Battery heavily discharged Low Battery Volts Check battery connections Check battery fuse Check battery...

Страница 11: ...e header marked OP1 OP2 This mode meets the requirements of EN54 13 Section 5 3 3 1 SFAULT and Section 5 3 4 2 PFAULT warning conditions for loads above 200mA It is still necessary for the connected equipment to be designed to accept two separate power inputs such that a short to ground of either power transmission path will not inhibit the equipment performance PSU Addressable Data link communica...

Страница 12: ...ery type information The battery is marked with the crossed out wheelie bin symbol which may include lettering to indicate cadmium Cd lead Pb or mercury Hg For more information see www recyclethis info The packaging supplied with this product may be recycled Please dispose of packaging accordingly COMPLIANCE This power supply unit meets the essential requirements of the following EU Directives CPR...

Отзывы: