(follow steps 29-30). Once the batteries are charging, clear the thermistor fault by reconnecting the
thermistor wire.
32.
Verify GEN Fault relay n/c contact is
closed
, (com to n/c terminals = short circuit)
33.
Disconnect the mains power. Verify that the green Mains LED #1 extinguishes, and the Yellow Fault LED
#3 starts to flash (indicating that the PSE is running from its standby batteries).
34.
If connected, verify that the EPS Fault output shows an
open
contact (com and n/c terminals = open
circuit) and the GEN PSU Fault output shows a
closed
contact (com and n/c terminals = short circuit).
35.
Verify that the standby batteries are now supporting the system load. Perform a full functional test of
system including full alarm condition Note: ensure batteries have sufficient charge to support the
system under full load.
36.
To prevent battery fault indication when no battery
is required, fit the “No Battery” link ( ).
Please note; fitting of this link invalidates EN54-4,
EN12101-10 and NF S 61-940 compliance.
Final Commission
37.
Reconnect the mains. Verify that
LED #
Symbol
LED Colour
Function
1
Mains
Constant Green
Indication: Mains supply = OK
2
Batt
Green flash x1
(repeating)
Indication: Battery Charging (bulk phase)
3
Fault
OFF
Indication: No Fault
4
Diagnostic
OFF
Indication: No Fault
5
OP1
Constant Green
Indication: Output 1 = OK
6
OP2
Constant Green
Indication: Output 2 = OK
(See also ‘
Status and Fault-Diagnostic LED Indication
‘ table for full details of LED indications.)
38.
If connected, verify that EPS Fault output shows a (com to n/c)
closed
contact and the GEN PSU Fault
output also shows a (com to n/c)
closed
contact.
39.
Disconnect one of the battery leads, ensuring that no exposed section of conductor or connector is
allowed to contact exposed metal-work, other PSE terminals, or other battery terminals.
40.
Verify that, in less than 1 minute the following conditions are met:
LED #
Symbol
Green ON
Function
1
Batt
Constant Yellow
Indication: Battery Fault = missing battery indicated
2
Fault
Yellow flash x1 (repeating
Indication: Fault with PSU = due to missing battery
3
Diagnostic
Red flash x2 (repeating)
Indication: Fault = missing battery indicated
4
OP1
Constant Green
Indication: Output 1 = OK
5
OP2
Constant Green
Indication: Output 2 = OK
6
Batt
Constant Yellow
Indication: Battery Fault = missing battery indicated
(See also ‘
Status and Fault-Diagnostic LED Indication
’
table for full details of LED indications.)
41.
Reconnect the battery lead and, after approximately 3s, verify that that the Fault LED #3 does not flash.
(Audible click can be heard as the battery relay closes, then a second click while the charger is tested.)
Note: If it is necessary to obtain confirmation of charging current; between steps 28 and 29, an ammeter
can be placed in series with the battery leads. Continue to observe caution with all exposed conductors
when inserting or removing the meter and when restoring normal battery wiring
42.
Close cover and secure using fastening screws provided.
- + -