1.10.
Status Indicator Codes
Code
Description
Status solid green, with fault off indicates that the device is connected via
Ethernet
Status 95% green, 5% off, with fault off indicates that the device is
connected via Wi-Fi.
Status 50% green, 50% off, with fault off indicates that the device is in
access-point mode. Connect to the device with a mobile phone or other
wireless device to configure a wireless network, or plug in an Ethernet cable.
One periodic red flash indicates that networking is not working properly, but
the device is otherwise functional. The RS-485 port may still be used in this
state.
Ensure that the Ethernet cable is connected, if used, and that there is a
networked path from the WattsOn-MCM to the DHCP server (usually the
router). If Wi-Fi is used, ensure that the wireless network is up and running
and that the SSID and Password last programmed into the device are
correct.
Two periodic red flashes indicates that the last web post has failed. This may
be temporary, or indicate a configuration problem with the WattsOn-MCM or
the server.
Fault solid red with status flashing indicates that a fault with one or more of
the installed nodes. A node may have failed, or may have been unexpectedly
removed. The other non-faulted nodes continue to function normally.
The Web Interface will show details about which node has faulted, if
possible. The status LED on the faulted card may also be blinking green and
red, or be off. Try re-seating this card in its PCI slot, or replacing it.
Fault solid red with status off indicates a fault that prevents the entire
WattsOn-MCM from metering. The web interface is normally still functional,
though metering data cannot be read in this state. This can happen when
communication with the nodes has failed, or the voltage cannot be read.
Ensure that the WattsOn-MCM-V is on and its status LED is green, and that
the status LEDs of all of the installed cards are solid green. Try removing or
re-seating any device with an off, red, or blinking green/red status LED. If all
are green, try removing each card, one at a time, and waiting 15 seconds
each time to see if the fault light clears; if the fault clears in this way, try re-
seating or replacing that node.
Repeated red flashes in a "
…
---
…
" pattern with status off indicate that the
WattsOn-MCM master device has suffered a fault is not functioning. The
firmware may be corrupt, or the hardware may be damaged.
FAULT
FAULT
STATUS
STATUS
FAULT
FAULT
STATUS
FAULT
STATUS
STATUS
STATUS
STATUS
STATUS
STATUS