ELKOR TECHNOLOGIES INC.
- Page 29 -
MCM
–
USER MANUAL
4.5.
Voltage Parameters
The following registers provide voltage and frequency information.
Starting
Offset
Register
Count
Length
(bytes)
Type Description
0x60F0
1
4
F
Voltage A
0x60F2
1
4
F
Voltage B
0x60F4
1
4
F
Voltage C
0x60F6
1
4
F
Voltage AB
0x60F8
1
4
F
Voltage BC
0x60FA
1
4
F
Voltage CA
0x61A8
1
4
F
Frequency
0x6278
1
2
U
PT Ratio A Primary
0x6279
1
2
U
PT Ratio A Secondary
0x627A
1
2
U
PT Ratio B Primary
0x627B
1
2
U
PT Ratio B Secondary
0x627C
1
2
U
PT Ratio C Primary
0x627D
1
2
U
PT Ratio C Secondary
0x6378
1
4
F
Voltage Angle AB
0x637A
1
4
F
Voltage Angle BC
0x637C
1
4
F
Voltage Angle CA