© 27.04.2005 ELKA-Torantriebe GmbH u. Co. Betriebs KG                     Page 9  

                                   EST 4004K 

 

Automatic closure for partial (pedestrian) opening. 

DIP A5 OFF 

Automatic closure is off. 

 

DIP A5 ON 

Automatic closure for the pedestrian position is enabled. 

If the gate is at the pedestrian position, BTG restarts the time to stay open. The gate opens 

completely if BA1 or BA2 is pressed. The gate closes immediately if BT or BZ is pressed. 

 
 
 

 
Automatic closure for completely open. 

DIP A6 OFF 

Automatic closure is off. 

 

DIP A6 ON 

Automatic closure from the open position is enabled. 

 

If the gate is in open position BA1 or BA2 restart the time to stay open. The gate closes 
immediately if BT or BZ are pressed when the gate is open. The gate reopens if BT is 
pressed during closing. 

 
 
 

 
Warning prior to opening 

DIP B1 OFF 

No warning. 

 

DIP B1 ON 

The warning light is switched on 4 seconds before the gate opens. 

 
 
 
 
Warning prior to closing 

DIP B2 OFF 

No warning. 

 

DIP B2 ON 

The warning light is switched on 4 seconds before the gate closes. 

 
 
 

 
Locking relays / Dead man’s button 

DIP B3 OFF 

The control box works with locking relays. 

 

DIP B3 ON 

BA1, BA2 and BZ are dead man’s buttons. (The opener stops as soon as the button is 
released). 

 
 
 

 
Delayed closing 

DIP B4 OFF 

The opening gate closes immediately when BZ is pressed. 

 

DIP B4 ON 

If the gate is opening and BZ is pressed, the signal is stored until the gate is open and then 
carried out. 

 
 
 

 
Three-phase operation

 

DIP B5 OFF 

Drive with single-phase motor (with electronic brake) 

DIP B5 ON 

Three-phase motor (with reversing contactor and mechanical brake) 

 
 
 

Содержание EST 4004K

Страница 1: ...ST 4004K Contents Page 1 Usage 2 2 Technical data 2 3 Measurements 2 4 Installation 3 4 1 Emergency release 4 5 Electrical connections 4 6 Connection example 5 7 MO 44 2 Controller 6 7 1 Connections 7...

Страница 2: ...ply 400 Vac 50 Hz Power consumption 2 2 kW Control box MO44 2 Electronic brake no The MO 44 2 control box has among others the following characteristics Safety Four separate reactions to the photo cel...

Страница 3: ...on parallel to the gate at a distance of 60 mm Mark the middle of each hole on the foundation e Fix the opener either with plugs and screws M20 or with heavy duty tie bolts e Decide at what height the...

Страница 4: ...ose the gate and push the holding plate with magnet along the rack until the LED SEZ turns off Fix the holder at this point on the rack so that the magnet passes the housing at a distance of about 10...

Страница 5: ...27 04 2005 ELKA Torantriebe GmbH u Co Betriebs KG Page 5 EST 4004K 6 Connection example...

Страница 6: ...27 04 2005 ELKA Torantriebe GmbH u Co Betriebs KG Page 6 EST 4004K 2T1 1L1 1L1 2T1 14NO 6T3 4T2 A2 13NO 5L3 3L2 K2 A1 6T3 4T2 14NO A2 5L3 3L2 K1 13NO A1 loop BA1 STOP START 7 MO 44 2 Controller...

Страница 7: ...itted to terminal EXT AUF The LED BA lights if BA1 or the corresponding remote button is pressed A permanent open signal is possible BA2 Button to open the gate n o the signal is valid only for this c...

Страница 8: ...tputs 300 mA LS TST Power supply for transmitter The controller switches the 24 Vdc on terminal LS TST off 7 2 Operating mode Motor power Changes only take effect if the running time is then learned a...

Страница 9: ...when the gate is open The gate reopens if BT is pressed during closing Warning prior to opening DIP B1 OFF No warning DIP B1 ON The warning light is switched on 4 seconds before the gate opens Warnin...

Страница 10: ...e relay connections of the receivers have to be connected in series Parallel to the relay connections a resistor of 1kOhm 5 each has to be connected The photo cell test consists of two parts The trans...

Страница 11: ...N until the LED DIAG lights approx 3 seconds Press LERN twice The gate closes from any position opens completely and closes again The time required and the power selected DIP A1 and DIP A2 are then sa...

Страница 12: ...The LED DIAG stays on as long as a signal is received Release the button The code is stored and the controller is ready for use 8 Timer card optional The 7 day timer can switch between day and night...

Страница 13: ...DIAG 11 flashes The controller has detected a fault in the redundant detection of BS stop contact The controller is faulty DIAG 12 flashes The controller detects that the TRIAC or one of motor relays...

Страница 14: ...e GmbH Co Betriebs KG accepts no liability for damage which is caused by using the appliance for purposes other than those for which it is built ELKA Torantriebe GmbH Co Betriebs KG cannot recognise e...

Отзывы: