© 27.04.2005 ELKA-Torantriebe GmbH u. Co. Betriebs KG Page 11
EST 4004K
LT
LT
LT
LT
LT
BT
BT
BT
BT
BT
BT
BTG
BTG
BTG
BTG
LT
Funk
Funk
Funk
running time
is stored
all personal
codes are
erased
position for
partial opening
is stored
remote code
for BA1 is
stored
time to stay for
position open
is stored
press 3s
Diag-LED lights
Diag-LED flashes
quickly
Diag-LED lights,
gate opens and
closes, 10 s
reserve are set
Diag flashes
Diag-LED
flashes each
second, set
new reserve
Diag-LED
lights
Diag-LED
lights, BTG is
deadman
button, move
to partial open
position
gate closes
Diag-LED
lights for 3s
Diag-LED
flashes each
second, set
time to stay
open
Diag-LED flashes
quickly
Diag-LED flashes
quickly
Diag-LED
lights for 3s
Diag-LED
lights for 3s
Diag-LED
flashes each
second, set
time to stay
open
remote code
for BT is
stored
time to stay for
partial open is
stored
remote code
for BTG is
stored
7.3. Programming
The minimum to ensure that the opener works correctly is that the running time must be learned. Other
things like automatic closure, or time which the gate should stay open before closing can also be set during
programming.
The following settings can be altered if required:
Time required to open (running time)
(0...150 s,
default 30 s)
Reserve for the running time
(0...10 s,
default 10 s)
Time to stay open before automatic closure
(0...300 s,
default 20 s)
Time to stay open before automatic closure from partial position
(0...300 s,
default 20 s)
Position for partial opening for pedestrians
(any position, default half way)
Remote control codes for BT, BTG and BA1
(default BT -+-+...)
Learning the time for opening (running time) and reserve
Press LERN until the LED DIAG lights (approx. 3 seconds).
Press LERN twice.
The gate closes from any position, opens completely and closes again. The time required and the power
selected (DIP A1 and DIP A2) are then saved. The LED DIAG starts flashing quickly, the running time is
learned. Press LERN if you want to accept the default value for the running time reserve (10 s). The
controller is ready for use.
If you want to change the running time reserve press BT, the LED DIAG flashes in 1 second intervals, press
BT when the required time has elapsed. The controller is ready for use.
The position for partial opening is automatically set to half way when the running time is learned, this means
that any other value for pedestrian opening must be learned after the running time!
Learning partial opening for pedestrians
Press LERN until the LED DIAG lights (approx. 3 seconds).
Press
LERN once. The LED DIAG flashes quickly.
The BTG button moves the gate in dead mans mode. When the gate is at the required position press LERN.
The gate closes automatically and the information is stored. The controller is ready for use.
Learning the time to stay open before automatic closure (completely open)
Press LERN until the LED DIAG lights (approx. 3 seconds).
Press BT twice. The LED DIAG flashes in 1 second intervals.
When the time required has elapsed press BT again.
The time is stored and the controller is ready for use. The time is only effective when automatic closure is on
(DIP A6 ON).
Learning the time to stay open before automatic closure (partial opening for pedestrians)
Press LERN until the LED DIAG lights (approx. 3 seconds).
Press BTG twice. The LED DIAG flashes in 1 second intervals.
When the time required has elapsed press BTG again.
The time is stored and the controller is ready for use. The time is only effective when automatic closure is on
(DIP A5 ON).