M1XSP Installation Manual
Page 32
ELK-WO46A Cable Pin-out and Color Coding
DB9F female Connector
Wire Color
Pin 2 connects to ........................................... RED
Pin 3 connects to ...................................... GREEN
Pin 4 connects to .................... WHITE (alt. Yellow)
Pin 5 connects to ....................................... BLACK
Pins 1, 4, and 6 (DCD, DTR, and DSR) jump together.
Pins 7 & 8 (RTS and CTS) jump together.
Brand & Model
Format
Baud Rate
M1 Max. Thermostats
Required Number of M1XSP and Other Equipment
RCS TR-16
RS-485
Auto 9600
16
1 M1XSP for all thermostats
RCS TR-40
RS-485
Auto 9600
16
1 M1XSP for all thermostats
RCS TR-16
RS-232
Auto 9600
7
RCS 232 format requires 1 M1XSP per Thermostat
Aprilaire 8870
RS-485
Auto 9600
16
1 M1XSP + 8811 Adapter & 8818 Dist. Panel required
HAI RC Series
RS-232
Auto 300
16
1 M1XSP for every 4 thermostats
**
Carrier Infinity
RS-232
38,400
16
1 M1XSP for all thermostats
**
IMPORTANT: When interfacing with HAI Thermostats, only data bus addresses 1, 2, 3, or 4 are used. Data bus address
1 is used for HAI Thermostats numbered 1 thru 4. Data bus address 2 for HAI Thermostats numbered 5 to 8. Data bus
address 3 for HAI Thermostats numbered 9 to 12. Data bus address 4 for HAI Thermostats numbered 13 to 16.
THERMOSTAT COMPATIBILITY CHART
Pin-out requirements for RS232 9 Pin Serial (DB9M male to
DB9F female) Cable
The M1XSP requires only 3 wires to be connected:
Connector
Connector
DB9M male
Wire Color
DB9F female
Pin 2 connects to ............. N/A ........................ Pin 2
Pin 3 connects to ............. N/A ........................ Pin 3
Pin 5 connects to ............. N/A ........................ Pin 5
M1XSP options are set by the placement of black shorting plugs on gold plated jumper pins . Some have 3 pins with a selection of "0" or "1".
Some have only 2 pins with a selection of Off or On. Options vary by manufacturer. Refer to detailed installation and hookup diagrams.
** Jumper S4 for future expansion, shown for reference only. Current M1XSPs do not provide this jumper.
The equivalent value of position S4 with no jumper is a 1.
Jumper S5 was not included on very early product units.
* In the INSTEON mode S5 has an alternate setting of
1
to allow more X-10 units in lieu of INSTEON groups.
$ For S8 selects whether a "request node status" (poll) command is sent.
Other Jumper Settings
JP1
Used to engage a 120 Ohm resistor for terminating the M1 RS-485 Data Bus. See M1 Data bus wiring instructions before use.
JP2
Used to engage a 120 Ohm resistor for terminating the 'Outbound' (External) RS-485 Data Bus if required by other manufacturer.
JP3
Selects either RS-232 or RS-485 format communications on the 'Outbound' connections. Jumper Left = RS-232, Jumper Right = RS-485
JP4
Not used
JP5
Used to 12V to pin 4 (DTR) of the DB9 Female connector for certain modes. This jumper can typically be left on always.
Jumper
Settings
S1
S2
S3
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
BAUD
Rate
110
300
1200
2400
4800
9600
19,200
38,400
IMPORTANT! Several partner interfaces require the M1XSP to be downloaded (flashed) with
dedicated firmware as noted above. Refer to the M1 Dealer Website for most recent firmware
versions. The above chart represents the most recent firmware versions and compatibility.
Information subject to change without notice.
Partner Interface
Settings for Jumpers
Special setup, notes, and comments
Communications Speed
(Mfg or function)
** (S4 for future use)
S4
S5
S6
S7
S8
Serial Port Exp.
-
1
0
0
0
Set BAUD Jumpers according to desired speed.
RCS Thermostat
-
1
0
0
1
Set JP3 to 232 or 485 depending on RCS model
9,600 Baud
HAI OmniStat 1 (RC)
-
1
0
1
0
JP5 must be "ON"
.
300 Baud
HAI OmniStat 2
-
1
0
1
0
Use firmware ver. 70.x.x
JP5 must be "ON"
2,400 Baud
Aprilaire Thermostat
-
1
0
1
1
9,600 Baud
Carrier Infinity HVAC
-
1
1
1
1
Use firmware ver. 40.x.x
JP5 must be "OFF"
38,400 Baud
OnQ-ALC
-
1
1
0
0
9,600 Baud
UPB
-
1
1
0
1
JP5 must to "ON"
4,800 Baud
Centralite "LiteJet/Eleg"
-
1
1
1
0
19,200 Baud
Centralite "JetStream"
-
1
1
1
0
Use firmware ver. 30.x.x
JP5 must be "OFF"
19,200 Baud
EDT - iLine
-
1
1
1
1
Supported ONLY by firmware 1.0.26 or earlier
9,600 Baud
Uplink "AnyNET" Radio
-
0
0
0
0
Use firmware ver. 10.x.x
JP5 must be "OFF"
9,600 Baud
AES Intellinet Radio
-
0
0
0
1
Use firmware ver. 10.x.x
4,800
Baud
[future]
-
0
0
1
0
INSTEON
-
0 * 0
1
1
Use firmware ver. 50.x.x
* Set Baud Jumpers to 111
HPM (australia)
-
0
1
0
0
4,800 Baud
Dynalite (australia)
-
0
1
0
1
RS-485 (Command Only - No Status Received)
9,600 Baud
Lutron Radio RA
-
0
1
1
0
9,600 Baud
WGL W800RF32
-
0
1
1
1
W800RF32 receives X10 RF devices
4,800 Baud
Leviton
-
-
-
-
$
Use firmware ver. 20.x.x
JP5 must be "OFF"
n/a
M1XSP Compatibility, Jumper Settings and Misc. Information