M1XSP Installation Manual

Page 16

Elegance and LiteJet - 

Low voltage, centrally controlled lighting.  All lights to be controlled are high voltage home run back to a dimmer/relay

enclosure.  This enclosure contains an MCP Processor Board with an on-board RS232 serial port for interfacing with the M1XSP.  Depending on
the particular Centralite model, the M1XSP can support up to 192 individual light devices (loads) and up to 64 lighting scenes.

Centralite StarLite and JetStream 

- Wireless lighting control.  The M1XSP interfaces to a Centralite Master Interface or RS232 Bridge which

then wirelessly controls switches installed around the building.  Depending on the model, up to 96 individual light devices (loads) and up to 64
lighting scenes can be controlled.

IMPORTANT: The M1XSP requires firmware version 30.x.x to support JetStream. 

 This firmware is downloadable from the

Elk M1Dealer website.  Select the M1XSP Firmware and look for the appropriate JetStream file.  

Starlite utilizes standard M1XSP

firmware 

(same as for LiteJet), however DIP switch #7 on the Starlite MCP must be set to ON so that Starlite will know to emulate

the LiteJet protocol.

Integration:

Integration with the M1 is accomplished by "mapping" the Centralite loads to M1 Lighting devices.  For example:  Centralite individual load 1 is
mapped to M1 Lighting devices 1.  Scenes start at M1 Lighting device 193 and go up.  E.G. Scene 1 is mapped as M1 Lighting device 193.  The
chart shows the M1 Lighting devices and their corresponding Centralite Load/Scenes.

Components required:

-

An ELK-M1 or ELK-M1EZ8 Controller.

-

One (1) ELK-M1XSP Serial Port Expander.  NOTE: Firmware updates may be downloaded from the ELK M1 Dealer Web site.

-

Centralite LiteJet or Elegance with MCP processor board, JetStream with RS232 Bridge, or Starlite with MCP base unit.

-

One or more Centralite lighting devices and/or switches.

Setting up the M1XSP and the M1 to communicate with Elegance, LiteJet, or Starlite

1.

Install the ELK-M1XSP per the instructions on page 3.  Be sure to enroll the device into the M1.

2.

Connect the 9-pin serial cable between the M1XSP and serial connector on the Centralite MCP processor board marked "RS232-2".

3.

Set M1XSP 

MODE

 Jumpers to: 

S4="1" (UP), S5="1" (UP), S6="1" (UP), S7="1" (UP), S8="0" (DN).  

NOTE: Some units do not have jumper

S4.

4.

Set the M1XSP Jumper 

JP3="232"

.   The position of BAUD jumpers S1,S2,S3 does not matter.

5.

Power up all the devices.

6.

Program the M1 Lighting device attributes utilizing the ElkRP software.  Only the specific devices to be used for Centralite need to be
programmed.  For individual addresses program M1 Lighting devices:  

1-192 "Format=Serial Expander" and "Type= Dimmer" (Type

may also be programmed as "On/Off Switch" if the device isn't dimmable)

.   For the scene addresses program M1 Lighting

devices: 

193-256 as "Format= Serial Expander", "Type=On/Off Switch"

.

Load Status and/or Limitations with Elegance and LiteJet:

-

The wallplate "button press" feature with LiteJet & Elegance is not directly usable with M1.  However, by assigning a button to a load, even
a phantom (non-physical) load, it may be possible to use the status change of that load as a trigger with M1.

-

To receive load status changes from Centralite the 

M1XSP MUST have firmware ver 1.0.14 or later

 and the Centralite Main Processor

MCP MUST have firmware ver 5.5 or later

.  There is a status Dipswich that must be set on the MCP.  On the Elegance MCP Dipswitch

#5 must be set to ON.  On the LiteJet MCP Dipswitch #6 must be set to ON.  NOTE: DO NOT software program the load option  to "send
changes".  The Dipswitch settings will take care of this feature.

Note: Version 5.5 or later of the Centralite firmware places a 1

second delay between each load change transmission.  This means that multiple load changes can and will take several
seconds to reach the M1.  An ALL ON command could take well over a minute for all loads to report in.

-

Please note that under some conditions it may not be possible to obtain instantaneous real time lighting status updates.

Setting up the M1XSP and the M1 to communicate with JetStream

1.

Install the ELK-M1XSP per the instructions on page 3.  Be sure to enroll the device into the M1.

2.

Download M1XSP firmware 30.x.8 (or later) from the Elk M1Dealer website and flash update the M1XSP.  

IMPORTANT!

3.

Connect the 9-pin serial cable between the M1XSP and serial connector on the JetStream RS232 Bridge.

4.

The M1XSP 

MODE

 Jumpers S1 to S8 are NOT APPLICABLE with this firmware and do not need to be changed or set.

5.

Set the M1XSP Jumper 

JP3="232"

.   The position of BAUD jumpers S1,S2,S3 does not matter.

6.

If there is a shorting Jumper on JP5 remove it.

7.

Power up all the devices.

6.

Program the M1 Lighting device attributes utilizing the ElkRP software.

JetStream Configuration, Load Status and Limitations:

1.

Install the JetStream devices into a "network" and program them using the JetStream USB programming dongle.
Follow the User's or Programming guide which came with the CentraLite JetStream system.

2.

Add the RS-232 Bridge to the network.   Refer to the section titled “Bringing the RS-232 Bridge into the Network” and “Configuring the
RS-232 Bridge for Your Area".  Also the section “Third Party Control”.  Verify that the baud rate for the RS232 bridge is set for 19200.

3.

To get status updates the following steps MUST be performed:

a. Select the RS-232 Bridge in the Device List on the left hand side of the JetStream Software.
b. Check the box labeled “Update Third Party.”

4.

Once step 4 has been completed there will be a new checkbox option available on each lighting device page.  This option will be labeled
"Send T-Party".  Check this box for any and all devices that status report is desired.

5.

IMPORTANT!  Click Send Device or Send All to make sure all devices are updated with the latest changes.

Centralite   (Individual Lighting Loads and Scenes)

Содержание ELK-M1XSP

Страница 1: ...the capabilities or data definitions to permit additional integration beyond what is currently available In addition Partner Mfgs may at their option add modify or discontinued features or support wit...

Страница 2: ...ettings via DIP Switches Jumper Options and LED Diagnostic indicator On Board EOL Bus Termination Jumper Flash Memory for Firmware Updating SPECIFICATIONS Maximum of Expandable Ports Units 7 with M1G...

Страница 3: ...HAI Thermostats numbered 1 thru 4 Data bus address 2 for HAI Thermostats numbered 5 to 8 Data bus address 3 for HAI Thermostats numbered 9 to 12 Data bus address 4 for HAI Thermostats numbered 13 to 1...

Страница 4: ...AI OnQ ALC UPB Centralite EDT Dynalite LutronRA W800RF32 etc 10 x x Field Installable Firmware Uplink AnyNet and AES Intellinet Radio 20 x x Field Installable Firmware Vizia RZCOP ZWave interface Down...

Страница 5: ...Aprilaire baud rate is preset internally 4 Plug the Aprilaire supplied 6 ft RJ to DB9 Cable between the 8811 Protocol Adapter and the ELK M1XSP DO NOT USE THE ELK WO37A CABLE 5 Power up the Aprilaire...

Страница 6: ...unit The White Yellow wire is optional It may be used to supply 12VDC from the M1XSP to the Thermostat in lieu of the HVAC power Consult the RCS manual for details Plug the other end of the ELK WO37A...

Страница 7: ...preset internally 4 Using a 3 conductor cable and the diagram below connect the GND D and D wires from the RS 485 terminals on the RCS Thermostat Control unit to the RS 485 terminals on the M1XSP The...

Страница 8: ...OmniStat 2 series the M1XSP must be firmware updated to version 70 0 2 or the latest 70 x x version 4 Set the M1XSP MODE jumpers to S5 1 S6 0 S7 1 S8 0 If the M1XSP has jumper S4 set it to 1 5 Set th...

Страница 9: ...Data Bus Terminals VKP A B Neg ADDRESS Only Addresses 1 2 3 or 4 can be used with HAI Stats Address 1 shown Switch 1 on MODE For HAI set to 1010 1 0 Address 1 2 4 8 ELK M1XSP Interface 1 0 1 2 3 4 RS...

Страница 10: ...assigned to Carrier System 2 Zone 2 Elk Thermostat 3 is assigned to Carrier System 1 Zone 3 Elk Thermostat 11 is assigned to Carrier System 2 Zone 3 Elk Thermostat 4 is assigned to Carrier System 1 Z...

Страница 11: ...T FORGET TO ENROLL THE M1XSP INTO THE M1 9 Program and test at least one light device using the ELK RP Software and the following steps 9a Click on the Automation icon then on the Lighting icon 9b Cli...

Страница 12: ...only support ALC 4 button scene switches wired and connected on ALC branch 1 Setting up the M1XSP and the M1 to communicate with OnQ ALC 1 Install the ELK M1XSP per the instructions on page 3 Be sure...

Страница 13: ...4 F15 F16 G01 G02 G03 G04 G05 G06 G07 G08 G09 G10 G11 G12 G13 G14 G15 G16 H01 H02 H03 H04 H05 H06 H07 H08 H09 H10 H11 H12 H13 H14 H15 H16 ELK Light Device 129 130 131 132 133 134 135 136 137 138 139 1...

Страница 14: ...individual addresses program M1 Lighting devices 1 192 as Format Serial Expander Type Dimmer or On Off Switch if the device isn t dimmable For UPB link addresses program M1 Lighting devices 193 256 a...

Страница 15: ...1 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J01 J02 J03 J04 J05 J06 J07 J08 J09 J10 J11 J12 J13 J14 J15 J16 K01 K02 K03 K04 K05 K06 K07 K08 K09 K10 K11 K12 K13 K...

Страница 16: ...pander Type On Off Switch Load Status and or Limitations with Elegance and LiteJet The wallplate button press feature with LiteJet Elegance is not directly usable with M1 However by assigning a button...

Страница 17: ...172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J01 J02 J03 J04 J05 J06 J07 J08 J09 J10...

Страница 18: ...nd 17 All On All Off respectively Program the name for light device 16 as All On Off Set the Format to Serial Expander and Type to On Off Switch Activating M1 lighting 16 On it will send Phantom 16 Ac...

Страница 19: ...2 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J...

Страница 20: ...nked learned into the M1XSP starting at the first M1 Lighting device 001 A1 Using just the M1XSP there is no way to have devices start at a specific location INSTEON devices cannot be removed or re ar...

Страница 21: ...e Right arrow key to access Menu 1 View Control Automation Fncts Press 2 followed by the right arrow key for the Lighting sub menu Advance to M1 Light 256 INSTEON LinkMode by entering 2 5 6 2 Turn ON...

Страница 22: ...s an option to eliminate Groups and free up addresses 193 M1 to 254 P14 See note N2 below N1 With the M1XSP Jumper S5 0 factory setting the M1XSP supports a total of 192 individual INSTEON or X 10 Lig...

Страница 23: ...H14 H15 H16 ELK Light Device 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 17...

Страница 24: ...s c RS 232 Setup this may show up as HAI SETUP in some older remotes For helpful information about the ViziaRF configuration use the following link to the Leviton web site http www leviton com OA_HTML...

Страница 25: ...be set as Backup B Optional Program a name to describe the location that this telephone number is reporting to C Do not program any numbers into the NUMBER TO DIAL location D Program the reporting for...

Страница 26: ...ignals onto the AC powerline if equipped with a PSC05 PLC interface Please note that M1 rules can only be activated by ON or OFF commands from these devices There is no rule activation support for DIM...

Страница 27: ...the AES Radio to be positioned far from the control 6 Construct a Serial Connection Cable from the M1XSP to the AES Radio Unit using the diagram below This cable requires a DB9F 9 Pin Female connecto...

Страница 28: ...ING ELKRP SOFTWARE MAKE SURE TO SEND ALL OF THIS PROGRAMMING TO THE CONTROL 10 Test Test Test It is very important to test each of the reported events SUPERVISION The M1XSP is enrolled with M1 Control...

Страница 29: ...esignated A and A1 Do the same for the data B White wire At the control splice the A1 and B1 wires to the A and B wires going to the next device Terminate the last wired device and the control JP3 ONL...

Страница 30: ...keys to exit Installer Programming 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 12345678...

Страница 31: ...M1XSP InstallationManual Page 31 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 32: ...engage a 120 Ohm resistor for terminating the M1 RS 485 Data Bus See M1 Data bus wiring instructions before use JP2 Used to engage a 120 Ohm resistor for terminating the Outbound External RS 485 Data...

Отзывы: