Televis

Out

 (Connections and Default applications)

Televis

Out

100-240V

a

+

}

}

8

9 10 11 12

No.

Label

Description

1-2-3

RS-485

Serial RS-485 (1 = "-"; 2 = "+" and 3 = "GND")

6

C

Common

7

OUT1

NO relay output OUT1 - high voltage (2A - 230V

a

)

8

OUT2

NO relay output OUT2 - high voltage (2A - 230V

a

)

9

OUT3

NO relay output OUT2 - high voltage (2A - 230V

a

)

10

OUT4

NC relay output OUT4 - high voltage (2A - 230V

a

)

11

OUT4

Common relay output OUT4 - high voltage (2A - 230V

a

)

12

OUT4

NO relay output OUT4 - high voltage (2A - 230V

a

)

OUT5/DI1

Low voltage digital input 1, also configurable as Analogue Output 
OUT5 - low voltage (SELV) OC: PWM

OUT6/DI2

Low voltage digital input 2, also configurable as Analogue Output 
OUT6 - low voltage (SELV) OC: PWM

GND

Ground

12V

c

Auxiliary power supply 12V

c

23-24 Power supply  Power supply 100-240V

a

NOTES

*     Connect the terminal to one of the GND terminals.
**   SELV: SAFETY EXTRA LOW VOLTAGE

Function

Label

Parameters

AP1

AP2...AP8

Note

Input/Output

DI1 / OUT5

H11

Applications 

can be configured 

by users

  

Digital inputs DI1/DI2 are low voltage digital inputs 
and the closing current for ground is 0.5mA.

Input/Output

DI2 / OUT6

H12

Output

OUT1

H21

NO-LINK

Output

OUT2

H22

Output

OUT3

H23

Output

OUT4

H24

PASSWORDS

Password 

PA1

:  

allows access to the “User” parameters. By default the password is disabled (

PS1=0

).

Password 

PA2

:  

allows access to “Installer” parameters. By default the password is enabled (

PS2=0

).

 

(For more details, see the User Manual which can be downloaded from the Eliwell website).

The visibility of “PA2” is:
1) 

PA1

 and 

PA2≠0

:  Press and hold 

 for longer than 5 seconds to display 

PA1 

and 

PA2

. You can then decide whether to access 

the “User” parameters (PA1) or the “Installer” parameters (

PA2

).

2) 

Otherwise

 Password 

PA2

 is at the end of the level1 parameters. If enabled, it will be required when accessing the “Installer” 

parameters.

NOTE

: If the value entered is incorrect, label PA1/PA2 will be shown again and the procedure must be repeated. 

MACHINE STATE MENU

Press the 

 once to open this menu.

Use the 

 and 

 keys to browse the menu. Press 

 to access the parameters or values it contains.

The visibility of folders depends on the configuration:
 

• 

AL

: alarms (always present, if there are no active alarms, the display readsd  “

----

”)

 

• 

Pb

Pbx

 values (for configured inputs only) and 

dEP

 (dewpoint)

 

• 

di

:  DI state (configured inputs only)

 

• 

do

: DO state (configured outputs only)

Pb

di

 and 

do

 are only visible if there is at least one configured input/output.

PROGRAMMING MENU

To access the “Programming” menu hold down the 

 key for more than 5 seconds. If enabled, the instrument will request an 

access PASSWORD, either PA1 for “User” parameters or PA2 for “Installer” parameters (see “PASSWORD” section).

User

” parameters: 

 When accessed the display will show the first parameter (e.g. “

diF

”). Press 

 and 

 to scroll through all 

parameters in the current level. Select the desired parameter by pressing 

. Press 

 and 

 

to change it 

and 

 to save changes.

Installer

” parameters:   When accessed the display will show the first folder (e.g. “

diF

”).

(For the list of “Installer” parameters, see the User Manual which can be downloaded from the Eliwell website).

NOTE

:   It is strongly recommended that you switch the device off and on again each time parameter configuration is changed, 

in order to prevent the configuration and/or ongoing timings from malfunctioning.