Televis
Out
(Connections and Default applications)
Televis
Out
100-240V
a
+
–
}
}
8
9 10 11 12
No.
Label
Description
1-2-3
RS-485
Serial RS-485 (1 = "-"; 2 = "+" and 3 = "GND")
6
C
Common
7
OUT1
NO relay output OUT1 - high voltage (2A - 230V
a
)
8
OUT2
NO relay output OUT2 - high voltage (2A - 230V
a
)
9
OUT3
NO relay output OUT2 - high voltage (2A - 230V
a
)
10
OUT4
NC relay output OUT4 - high voltage (2A - 230V
a
)
11
OUT4
Common relay output OUT4 - high voltage (2A - 230V
a
)
12
OUT4
NO relay output OUT4 - high voltage (2A - 230V
a
)
OUT5/DI1
Low voltage digital input 1, also configurable as Analogue Output
OUT5 - low voltage (SELV) OC: PWM
OUT6/DI2
Low voltage digital input 2, also configurable as Analogue Output
OUT6 - low voltage (SELV) OC: PWM
GND
Ground
12V
c
Auxiliary power supply 12V
c
23-24 Power supply Power supply 100-240V
a
NOTES
* Connect the terminal to one of the GND terminals.
** SELV: SAFETY EXTRA LOW VOLTAGE
Function
Label
Parameters
AP1
AP2...AP8
Note
Input/Output
DI1 / OUT5
H11
Applications
can be configured
by users
•
Digital inputs DI1/DI2 are low voltage digital inputs
and the closing current for ground is 0.5mA.
Input/Output
DI2 / OUT6
H12
Output
OUT1
H21
NO-LINK
Output
OUT2
H22
Output
OUT3
H23
Output
OUT4
H24
PASSWORDS
Password
PA1
:
allows access to the “User” parameters. By default the password is disabled (
PS1=0
).
Password
PA2
:
allows access to “Installer” parameters. By default the password is enabled (
PS2=0
).
(For more details, see the User Manual which can be downloaded from the Eliwell website).
The visibility of “PA2” is:
1)
PA1
and
PA2≠0
: Press and hold
for longer than 5 seconds to display
PA1
and
PA2
. You can then decide whether to access
the “User” parameters (PA1) or the “Installer” parameters (
PA2
).
2)
Otherwise
:
Password
PA2
is at the end of the level1 parameters. If enabled, it will be required when accessing the “Installer”
parameters.
NOTE
: If the value entered is incorrect, label PA1/PA2 will be shown again and the procedure must be repeated.
MACHINE STATE MENU
Press the
once to open this menu.
Use the
and
keys to browse the menu. Press
to access the parameters or values it contains.
The visibility of folders depends on the configuration:
•
AL
: alarms (always present, if there are no active alarms, the display readsd “
----
”)
•
Pb
:
Pbx
values (for configured inputs only) and
dEP
(dewpoint)
•
di
: DI state (configured inputs only)
•
do
: DO state (configured outputs only)
Pb
,
di
and
do
are only visible if there is at least one configured input/output.
PROGRAMMING MENU
To access the “Programming” menu hold down the
key for more than 5 seconds. If enabled, the instrument will request an
access PASSWORD, either PA1 for “User” parameters or PA2 for “Installer” parameters (see “PASSWORD” section).
“
User
” parameters:
When accessed the display will show the first parameter (e.g. “
diF
”). Press
and
to scroll through all
parameters in the current level. Select the desired parameter by pressing
. Press
and
to change it
and
to save changes.
“
Installer
” parameters: When accessed the display will show the first folder (e.g. “
diF
”).
(For the list of “Installer” parameters, see the User Manual which can be downloaded from the Eliwell website).
NOTE
: It is strongly recommended that you switch the device off and on again each time parameter configuration is changed,
in order to prevent the configuration and/or ongoing timings from malfunctioning.