SUPERVISION
The connection to supervisor systems is via the
RS-485
port and can use Televis or Modbus protocols.
The protocol to be used must be configured to ensure the proper function of Televis
In
and/or Televis
Out.
The parameters to be set
are in the “
Add
” folder, under the “Installer” parameters (see section entitled “Password”), as listed below.
N.B.
: 1) All communication parameters in the “Add” folder are not in the vectors.
2) A double terminal clip is provided as an RS485 connection accessory RS485
to connect two RS-485 in parallel.
COMMUNICATION PARAMETERS (Add)
PAR. Description
UM
Range
Value
PtS
Select protocol (
t
= Televis;
d
= ModBus).
flag
t/d
t
dEA Device address: indicates the device address to the management protocol.
num
0 ... 14
0
FAA Family address: indicates the device family to the management protocol.
num
0 ... 14
0
Adr
Modbus protocol controller address
num
1 ... 250
1
Pty
Sets Modbus parity bit (
n
= none;
E
= even;
o
= uneven).
num
n/E/o
n
StP
Sets Modbus stop bit: (
1b
= 1 BIT;
2b
= 2 BIT).
flag
1b/2b
1b
LOADING DEFAULT APPLICATIONS
The procedure for loading one of the default applications is:
• At power-on of the device, keep the
key pressed: the label “
AP1
” will appear.
• Scroll through the various applications (“
AP1
”... “
AP8
”) using the
and
keys.
• Select the application you want using the
key (“
AP3
” in the example) or cancel the operation
by pressing the
key or by timeout.
• If the operation is successful, the display will show “
y
”, if not it will show “
n
”.
• After a few seconds the instrument will return to the main display.
RESET PROCEDURE
Televis
In
& Televis
Out
can be RESET and the default factory settings restored in a simple and user-friendly way.
This is done by simply reloading one of the basic applications (see “Loading default applications”).
You may need to
RESET
the instrument in circumstances in which the normal operation of the instrument is compromised or if you
decide to restore the instrument to its default configuration (e.g. Application “
AP1
” values).
IMPORTANT
!
This operation resets the instrument to its initial state, returning all the parameters to their default values.
This means that all changes made to operating parameters will be lost.
Televis
In
(Connections and Default applications)
Televis
In
100-240V
a
+
–
}
}
}
No.
Label
Description
1-2-3
RS-485
Serial RS-485 (1 = “-”; 2 = “+” and 3 = “GND”)
6
C
Common
7
OUT1
NO relay output OUT1 - high voltage (2A - 230V
a
)
DI1
Digital Input 1
DI2
Digital Input 2
GND
Ground
12V
c
Auxiliary power supply 12V
c
PB1/DI3
Analogue input 1 configurable as: DI, NTC, PTC and PT1000
PB2/DI4
Analogue input 2 configurable as: DI, NTC, PTC and PT1000
PB3/DI5
Analogue input 3 configurable as: DI, NTC, V*** and I***
PB4/DI6
Analogue input 4 configurable as: DI, NTC, V*** and I***
PB5/DI7
Analogue input 5 configurable as: DI, NTC, PTC and PT1000
GND
Ground
23-24 Power supply Power supply 100-240V
a
NOTES
* Connect the terminal to one of the GND terminals.
** Analogue Inputs PB1...PB5 can also be configured
as DIs (H4x="DI")
*** The
V
and
I
configurable inputs (PB3 e PB4) are:
•
V = 0-1V; 0-5V and 0-10V
•
I = 0...20mA and 4...20mA
Function
Label
Parameters
AP1
AP2
AP3
AP4
AP5...AP8 Note
Input
DI1
H11
Applications can
be configured
by users
•
Use sensor SEMITEC 103 AT with
NTC analogue inputs (10KOhm /
25°C).
•
Digital inputs DI1/DI2 are low volt-
age digital inputs and the closing
current for ground is 0.5mA.
Input
DI2
H12
Input
Pb1 / DI3
H41, H13**
PTC
DI -
NTC
Input
Pb2 / DI4
H42, H14**
PTC
Input
Pb3 / DI5
H43, H15**
4...20mA
4...20mA
Input
Pb4 / DI6
H44, H16**
4...20mA
Input
Pb5 / DI7
H45, H17**
PTC
Output
OUT1
H21