SUPERVISION

The connection to supervisor systems is via the 

RS-485

 port and can use Televis or Modbus protocols.

The protocol to be used must be configured to ensure the proper function of Televis

In

 and/or Televis

Out.

 The parameters to be set 

are in the “

Add

” folder, under the “Installer” parameters (see section entitled “Password”), as listed below.

N.B.

: 1) All communication parameters in the “Add” folder are not in the vectors.

          2)  A double terminal clip is provided as an RS485 connection accessory RS485 

to connect two RS-485 in parallel.

COMMUNICATION PARAMETERS (Add)

PAR. Description

UM

Range

Value

PtS

Select protocol (

t

 = Televis; 

d

 = ModBus).

flag

t/d

t

dEA Device address: indicates the device address to the management protocol.

num

0 ... 14

0

FAA Family address: indicates the device family to the management protocol.

num

0 ... 14

0

Adr

Modbus protocol controller address

num

1 ... 250

1

Pty

Sets Modbus parity bit (

n

 = none; 

E

 = even; 

o

 = uneven).

num

n/E/o

n

StP

Sets Modbus stop bit: (

1b

 = 1 BIT; 

2b

 = 2 BIT).

flag

1b/2b

1b

LOADING DEFAULT APPLICATIONS

The procedure for loading one of the default applications is:
 

•  At power-on of the device, keep the 

 key pressed: the label “

AP1

” will appear.

 

•  Scroll through the various applications (“

AP1

”... “

AP8

”) using the 

 and 

 keys.

 

•   Select the application you want using the 

 key (“

AP3

” in the example) or cancel the operation

by pressing the 

 key or by timeout.

 

•   If the operation is successful, the display will show “

y

”, if not it will show “

n

”.

 

•  After a few seconds the instrument will return to the main display.

RESET PROCEDURE

Televis

In

 & Televis

Out

 can be RESET and the default factory settings restored in a simple and user-friendly way.

This is done by simply reloading one of the basic applications (see “Loading default applications”).
You may need to 

RESET

 the instrument in circumstances in which the normal operation of the instrument is compromised or if you 

decide to restore the instrument to its default configuration (e.g. Application “

AP1

” values).

IMPORTANT

This operation resets the instrument to its initial state, returning all the parameters to their default values. 

 

 

This means that all changes made to operating parameters will be lost.

Televis

In

 (Connections and Default applications)

Televis

In

100-240V

a

+

}

}

}

No.

Label

Description

1-2-3

RS-485

Serial RS-485 (1 = “-”; 2 = “+” and 3 = “GND”)

6

C

Common

7

OUT1

NO relay output OUT1 - high voltage (2A - 230V

a

)

DI1

Digital Input 1

DI2

Digital Input 2

GND

Ground

12V

c

Auxiliary power supply 12V

c

PB1/DI3

Analogue input 1 configurable as: DI, NTC, PTC and PT1000

PB2/DI4

Analogue input 2 configurable as: DI, NTC, PTC and PT1000

PB3/DI5

Analogue input 3 configurable as: DI, NTC, V*** and I***

PB4/DI6

Analogue input 4 configurable as: DI, NTC, V*** and I***

PB5/DI7

Analogue input 5 configurable as: DI, NTC, PTC and PT1000

GND

Ground

23-24 Power supply  Power supply 100-240V

a

NOTES

*     Connect the terminal to one of the GND terminals.
**   Analogue Inputs PB1...PB5 can also be configured
        as DIs (H4x="DI")
*** The  

V

 and 

I

 configurable inputs (PB3 e PB4) are: 

           

 V = 0-1V; 0-5V and 0-10V

           

 I = 0...20mA and 4...20mA

Function

Label

Parameters

AP1

AP2

AP3

AP4

AP5...AP8 Note

Input

DI1

H11

Applications can 

be configured 

by users

  Use sensor SEMITEC 103 AT with 

NTC analogue inputs (10KOhm / 
25°C).

•  

Digital inputs DI1/DI2 are low volt-
age digital inputs and the closing 
current for ground is 0.5mA.

Input

DI2

H12

Input

Pb1 / DI3

H41, H13**

PTC

DI - 

NTC

Input

Pb2 / DI4

H42, H14**

PTC

Input

Pb3 / DI5

H43, H15**

4...20mA

4...20mA

Input

Pb4 / DI6

H44, H16**

4...20mA

Input 

Pb5 / DI7 

H45, H17**

PTC

Output

OUT1

H21