Televis
Go
Page 7/68
2.2.3.2 Application information sheet
a)
Type of data logging
:
Suitable to save to archive.
b) General
requirements
:
- Measurement
range
: Network devices: use only class II rated devices (Eliwell)
- Supply voltage and frequency
: 12V DC with 100-240 V
±10%, 50-60 Hz ±3Hz power unit
- Power
failures
: Non-volatile internal memory, 10-year duration
c)
Requirements for metrological characteristics
:
- Maximum permissible errors, temperature measurement resolution and error
:
For network devices: depends on the devices
- Logging
interval
: configurable (default 15 minutes).
- Logging
time
: 1 year's worth of data guaranteed for 1500 analogue resources, at logging intervals of 15 minutes
- Maximum relative weather measurement error and weather recording error
<0.1%
- Response
time
: <30' with Eliwell controllers and Eliwell NTC probes
- Climate and influence of ambient temperature
: 'type A' in air
- Climate and temperature testing under logger storage and transportation conditions
: 'type A' in air
- Electrical disturbances and radiated electromagnetic field susceptibility
: conforms to EN55022 and EN55024
2.2.4 LANGUAGES SUPPORTED
The software features the following native languages:
• Italian
• English
• Spanish
• German
• French
Additional languages are available and can be requested from Eliwell.
On approval of the request, these languages can be installed separately.
2.3 COMPATIBILITY
2.3.1 BROWSERS SUPPORTED
Televis
Go
is compatible with the following browsers:
•
Internet Explorer 7 or later
•
Mozilla Firefox 3.5 or later
To speed up navigation
:
To make WEB navigation faster and more effective, we recommend:
1) Enabling the browser cache. This means pictures don't have to be reloaded at each connection, making navigation quicker and
more responsive.
IMPORTANT!
Incorrect configuration of the cache could lead to pages not being refreshed properly!
The following settings are recommended:
• Microsoft Internet Explorer:
•
Internet Options Window General Browsing History Settings
•
Check for newer versions of stored pages should be set to "Auto".
• Mozilla Firefox:
•
Tools window Advanced Network
•
Override automatic cache management must NOT be selected.
NOTE: Clear the cache every time the application has been updated
.
2) Use a browser that shows even partially loaded data before the whole page loads, which makes navigation quicker and more
responsive. For networks with over 700 resources, we recommend using browsers with more efficient JavaScript engines, such
as Firefox 3.5 or IE8 or later. This speeds up the introduction of and interaction with pages containing the network hierarchy (e.g.
Archived data selection / Naming / Network Summary / Offline).
2.3.2 TYPES OF NETWORK THAT CAN MONITORED
Televis
Go
has been approved for the following networks:
• “
RS-485”
networks and gateways using the SerialAdapter232 module (accessory can be purchased separately).
• “
LAN”
networks using the TCP/IP and gateways using the LAN Adapter module (accessory can be purchased separately).
The Eliwell guarantee extends to the correct use of only one type of network at a time. Some examples of usable networks are
provided below:
Содержание TelevisGo
Страница 4: ......
Страница 67: ...TelevisGo Page 67 68...